| 2021-01-20 12:20:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | OUTLETS IN EXAM ROOM TO BE WIRED PER 517.13 |
| | |
| | 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL |
| | EQUIPMENT IN PATIENT CARE SPACES. WIRING IN PATIENT |
| | CARE SPACES SHALL COMPLY WITH 517.13(A) AND (B). (A) |
| | WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT |
| | CARE SPACES SHALL BE PROVIDED WITH AN EFFECTIVE |
| | GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL |
| | RACEWAY SYSTEM OR A CABLE HAVING A METALLIC ARMOR OR |
| | SHEATH ASSEMBLY. THE METAL RACEWAY SYSTEM, METALLIC |
| | CABLE ARMOR, OR SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS |
| | AN EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH |
| | 250.118. (B) INSULATED EQUIPMENT GROUNDING CONDUCTORS |
| | AND INSULATED EQUIPMENT BONDING JUMPERS. (1) GENERAL. |
| | THE FOLLOWING SHALL BE DIRECTLY CONNECTED TO AN |
| | INSULATED COPPER EQUIPMENT GROUNDING CONDUCTOR THAT IS |
| | CLEARLY IDENTIFIED ALONG ITS ENTIRE LENGTH BY GREEN |
| | INSULATION AND INSTALLED WITH THE BRANCH CIRCUIT |
| | CONDUCTORS IN THE WIRING METHODS AS PROVIDED IN |
| | 517.13(A): (1) THE GROUNDING TERMINALS OF ALL |
| | RECEPTACLES OTHER THAN ISOLATED GROUND RECEPTACLES (2) |
| | METAL OUTLET BOXES, METAL DEVICE BOXES, OR METAL |
| | ENCLOSURES (3) ALL NON?CURRENT-CARRYING CONDUCTIVE |
| | SURFACES OF FIXED ELECTRICAL EQUIPMENT LIKELY TO BECOME |
| | ENERGIZED THAT ARE SUBJECT TO PERSONAL CONTACT, |
| | OPERATING AT OVER 100 VOLTS |