| 2021-01-20 10:41:50 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20120986 |
| | ADD: 2000 PALM BEACH LAKES BLVD. 5TH FLOOR. |
| | CONT: CAMPBELL GENERAL CONTRACTING, INC. |
| | TEL: 772-486-3764 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 20/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) SHEET AE101 THE FLOOR PLAN INDICATES THE BREAK ROOM |
| | AS ROOM # 527. WITHIN THE BREAKROOM THERE IS A COUNTER |
| | AND BREAKROOM SINK. THE FLOOR PLAN DOES NOT SHOW |
| | COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE FOR |
| | CLEAR FLOOR SPACE, EITHER A FRONT APPROACH OR SIDE |
| | APPROACH. |
| | 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE |
| | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED, |
| | SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED CLEAR FLOOR |
| | SPACE ON THE FLOOR PLAN. |
| | |
| | 2) SHEET AE101 THE FLOOR PLAN INDICATES THE BREAK ROOM |
| | AS ROOM # 527. THIS SHEET INDICATES DETAIL SHEET AE 501 |
| | DETAIL B SHOWS THE BREAK ROOM SINK & BASE CABINETS AT A |
| | HEIGHT OF 34 INCHES. A CUT SECTION THROUGH THE CABINET |
| | AE 501 DETAIL 2 SHOWS THERE IS NO SHELVING IN THIS |
| | CABINET BUT THERE IS A BOTTOM IN THE CABINET. ELEVATION |
| | B SHOWS A PAIR OF DOORS AT THE SINK WITH NO BOTTOM |
| | THERE IS A DISCREPANCY IN THE PLANS. IF A FRONT |
| | APPROACH IS TO BE INDICATED, PLEASE ALSO SHOW |
| | COMPLIANCE WITH SECTION 606.5 OF THE 2017 |
| | FBC-ACCESSIBILITY CODE. EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. |
| | |
| | 3) SHEET AE101 THE FLOOR PLAN INDICATES THE RESTROOM |
| | 526. SHEET AE 701 THE FINISH SCHEDULE INDICATES THE |
| | RESTROOM WALLS ARE TO HAVE A PAINT GRADE FINISH ON THE |
| | WALLS. |
| | |
| | 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT |
| | IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON |
| | 06/2020. IN RESTROOMS & SERVICE SINK AREAS EPOXY PAINT |
| | IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT |
| | SURFACE. |
| | |
| | 3A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 3B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 3C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 4) IT WOULD APPEAR THERE IS NO WORK TO BE COMPLETED IN |
| | THE COMMON LOBBY. THIS WHERE THE DRINKING FOUNTAIN IS |
| | FOUND. IT WOULD APPEAR THE EXISTING DRINKING FOUNTAIN |
| | IS A SINGLE FOUNTAIN. SHEET AE 702 DOES SHOW A PROFILE |
| | OF WHAT APPEARS TO BE A SINGLE DRINKING FOUNTAIN. |
| | NEITHER THE DETAIL NOR SINGLE DRINKING FOUNTAIN COMPLY |
| | WITH TODAYS 2017 ACCESSIBILITY CODE SECTION. NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. I DO |
| | NOT BELIEVE THIS CAN BE ENFORCED AT THIS TIME IF THERE |
| | IS NO WORK TO BE COMPLETE OUTSIDE OF THE TENANT SPACE, |
| | ( DRINKING FOUNTAIN IN THE COMMON AREAS), BUT THE |
| | DETAIL SHOULD EITHER BE REMOVED OR UPDATED FOR FUTURE |
| | USE. THE PLUMBING PLAN REVIEWER MAY HAVE MORE COMMENTS |
| | ON THIS MATTER. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |