Plan Review Notes
Plan Review Notes For Permit 20120964
Permit Number 20120964
Review Stop B
Sequence Number 3
Notes
Date Text
2022-06-27 15:03:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW/ 12/18/2020
 W. P. B. PERMIT: 20120964
 ADD: 1301 BELVEDERE RD.
 CONT: OCC CONSTRUCTION LLC/ CLARK S. HARDEN- QUALIFIER
 TEL: 561-281-0454
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JUNE 27TH/2022
 ACTION: DENIED
 6/27/2022 UNABLE TO READ ANY WRITING AND OR NOTES THIS
 SHEET LS-101. SHEET LS-102 NOT OPENING FOR REVIEW.
 UNABLE TO VERIFY THE INTEGRITY OF THE CONFIGURATION
 DATA, BIG RED NOTE. THE CLIENT ENCOUNTERED A PROBLEM
 WITH THE PREVIOUS REQUEST.
  
 1) THE LS-101 GROUND FLOOR LIFE SAFETY PLAN, A-102 &
 A-102A DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE, (SUBMITTED ON 12/18/2020 THE
 2020 FBC FAMILY OF CODES (ACCESSIBILITY INCLUDED) WAS
 ADOPTED STATEWIDE ON 12/31/2020.
  
 1A) SEMI-COMPLIED. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 1B)2ND REQUEST. THE HUDDLE SPOTS 123 AND HI-TOPS 128 DO
 NOT SHOW COMPLIANCE WITH THE HEIGHT REQUIREMENT FOUND
 IN 902.3 FOR DINING AND OR WORK SURFACES.
 1ST ROUND COMMENTS. 226.2 DISPERSION. DINING SURFACES
 AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 1C) COMPLIED.
  
 1D) SEMI-COMPLIED I DO NOT SEE A CUT SECTION THROUGH
 THE BAR SHOWING COMPLIANCE WITH 902.2 OR 902.3 OF THE
 2017 ACCESSIBILITY CODE. SEMI-COMPLIED.
 1ST ROUND COMMENTS. 902.1. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, HIGH TOPS, TABLES, LUNCH COUNTERS,
 AND BOOTHS. EXAMPLES OF WORK SURFACES INCLUDE WRITING
 SURFACES, STUDY CARRELS, STUDENT LABORATORY STATIONS,
 BABY CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 1E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1F)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1G-H) COMPLIED.
  
 2A) 6/27/2022 NOT ABLE TO VERIFY WITH LIFE SAFETY
 SHEETS NOT IN WORKING ORDER TO REVIEW.
 W SHEETS SEMI-COMPLIED. OCCUPANCY INDICATES HOTELS
 TRANSIENT R-1. MISSING OCCUPANCIES ARE EITHER:
 RESTAURANT A-2 OR BUSINESS LESS THAN 50 OCCUPANTS,
 BUSINESS: FRONT COUNTER AND ASSOCIATED OFFICE AREAS
 GYMNASIUM: A-3
 POOL AND POOL DECK: A-4
  
 MISSING THE SQUARE FOOTAGE FOR EACH OCCUPANCY TYPE,
 OCCUPANT LOAD FOR EACH OCCUPANCY.
 1ST ROUND OF COMMENTS. SHEET LS-102 2NSD FLOOR LIFE
 SAFETY PLAN. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION: 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS AND OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 CODE DATA/ BUILDING DATA
 OCCUPANCY GROUP
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2B)(1) RESPONSE STATES THAT FOR A R-1 HOTEL OCCUPANCY
 DRINKING FOUNTAINS ARE NOT REQUIRED PER THE 2017
 FBC-PLUMBING CODE. THIS IS TRUE BUT THE DRINKING
 FOUNTAINS ARE REQUIRED FOR A3 OCCUPANCY LECTURE HALLS,
 EXHIBITION HALLS AND AUDITORIUMS. DRINKING FOUNTAINS
 ARE ALSO REQUIRED FOR A4 OCCUPANCIES POOL AND POOL
 DECKS. A2 OCCUPANCIES RESTAURANTS AND BARS MAY NOT
 REQUIRE DRINKING FOUNTAINS IF THE PLAN STATES THEY ARE
 USING SECTION 410.4 WHERE RESTAURANTS PROVIDE DRINKING
 WATER IN A CONTAINER FREE OF CHARGE, THIS WAS NOTED ON
 THE LIFE SAFETY PLAN NOR PLUMBING SHEETS.
 THE OTHER ISSUE IS WITH SHEET A-106 ELEVATION 2
 DRINKING FOUNTAIN WITH BOTTLE FILLER. PLEASE SEE IN THE
 2017 FBC-PLUMBING CODE SECTION 410. 4 FOR SUBSTITUTION
 AND PLUMBING COMMENTS.
 1ST ROUND OF COMMENTS. 2017 FBC-ACCESSIBILITY CODE.
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 2ND REQUEST.(2B(2) PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 2ND REQUEST. 2B)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 2ND REQUEST. 2B)(4) SPOUT OUTLETS/ DRINKING FOUNTAINS.
 2017 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 3, 3A & 3B) N/A, NOT APPLICABLE. THIS PERMIT IS FOR
 INTERIOR RENOVATIONS ONLY. UNDER PARKING RE-SEALING/
 RESTRIPING SEPARATE PERMIT. CONTRACTOR LETTER DATED MAY
 12TH/ 2022.
  
  
 4)N/A. NOT APPLICABLE. THIS PERMIT IS FOR INTERIOR
 RENOVATIONS ONLY. CONTRACTOR LETTER DATED MAY 12TH/
 2022. AS-101A, POOL.
  
 5A) 2ND REQUEST. RESPONSE STATES THAT FOR A R-1 HOTEL
 OCCUPANCY DRINKING FOUNTAINS ARE NOT REQUIRED PER THE
 2017 FBC-PLUMBING CODE. THIS IS TRUE BUT THE DRINKING
 FOUNTAINS ARE REQUIRED FOR A3 OCCUPANCY LECTURE HALLS,
 EXHIBITION HALLS AND AUDITORIUMS. DRINKING FOUNTAINS
 ARE ALSO REQUIRED FOR A4 OCCUPANCIES POOL AND POOL
 DECKS. A2 OCCUPANCIES RESTAURANTS AND BARS MAY NOT
 REQUIRE DRINKING FOUNTAINS IF THE PLAN STATES THEY ARE
 USING SECTION 410.4 WHERE RESTAURANTS PROVIDE DRINKING
 WATER IN A CONTAINER FREE OF CHARGE, THIS WAS NOTED ON
 THE LIFE SAFETY PLAN NOR PLUMBING SHEETS.
 1ST ROUND OF COMMENTS. SHEET A-102 THE FITNESS ROOM 107
 SHOWS THE USE OF A WATER COOLER RATHER THAN DRINKING
 FOUNTAINS. 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 5B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 5C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5E) 211.3 MORE THAN MINIMUM NUMBER. WHERE MORE THAN THE
 MINIMUM NUMBER OF DRINKING FOUNTAINS SPECIFIED IN
 211.2ARE PROVIDED, 50 PERCENT OF THE TOTAL NUMBER OF
 DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND 50 PERCENT SHALL OF THE TOTAL NUMBER
 OF DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.7.
  
 6) DISPROPORTIONATE COST LETTER REVIEWED. THE 202.4.1.
 DISPROPORTIONATE COST IS FIGURED ON THE TOTAL CONTRACT
 VALUE, OVER AND ABOVE THE CONTRACT VALUE. THIS ISSUE
 HAS TO BE DISCUSSED WITH THE BUILDING OFFICIAL BEFORE
 FURTHER COMMENT. RESEALING & RESTRIPING OF THE PARKING
 LOT NOT INCLUDED IN CONTRACTOR COST BREAKDOWN NOR WERE
 THERE DOLLAR AMOUNTS SHOWN WHERE THE COST FOR
 DISPROPORTION MAKE UP 21% OF THE BUDGET.
 1ST ROUND OF COMMENTS. NEW COMMENT 11/09/2021 TO
 ADDRESS THE DESIGNER OF RECORD E-MAIL. FLORIDA
 ACCESSIBILITY CODE SECTION: DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% ($585,000.00 X
 0.20= $117,000.00 UP TO) DISPROPORTIONATE FUNDS LISTED
 FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN
 THE ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  