2022-04-12 16:53:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20120964 1301 BELVEDERE RD
  
 2ND REVIEW
 PLUMBING /GAS COMMENTS: DENIED
 THERE WAS NO RESPONSE OR ACKNOWLEDGEMENT OF THE
 PLUMBING/GAS COMMENTS FROM REVIEW 1.
  
 1.SECOND REQUEST: A SERVICE SINK IS REQUIRED PER FBC PL
 TABLE 403.1.
 TO BE CLEAR, REFER TO COMMENT 7 BELOW; PROVIDE A
 PLUMBING FIXTURE SCHEDULE NOTING REQUIRED PLUMBING
 FIXTURES AND QUANTITIES AS REQUIRED BY FBC PL TABLE
 403.1 FOR THE OCCUPANCY (OCCUPANCIES) AND THE ACTUAL
 FIXTURES AND QUANTITIES PROVIDED.
  
 2. SECOND REQUEST: PROPOSED LOBBY AREA HAS A LARGE
 DINING AREA AND PHYSICAL FITNESS ROOM AND APPEARS TO
 FIT THE DESCRIPTION FOR ASSEMBLY. PLAN SHEET T-001
 INDICATES R-1 OCCUPANCY. PER WPB FBC 107.2.1, CLARIFY
 OCCUPANCY TYPES AND LOADS.
  
 3. SECOND REQUEST: PROPOSED SECOND FLOOR IS MADE UP OF
 MEETING ROOMS, LOUNGE AREAS AND LECTURE HALLS AND
 APPEARS TO FIT THE DESCRIPTION FOR ASSEMBLY. PER WPB
 FBC 107.2.1, CLARIFY OCCUPANCY TYPES AND LOADS.
  
 4. SECOND REQUEST: PER FBC PL TABLE 403.1 AND FBC ACC
 211.2, PROVIDE DRINKING FOUNTAIN(S) COMPLYING WITH FBC
 PL 410.3 AND FBC ACC 602.1 THROUGH 606.7, 305, 306 AND
 307.2.
 PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING COMPLIANCE
 WITH FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 EXCEPTIONS:
 ...A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS
 THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE
 A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO
 BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS.
  
 5. N/A-PLAN SHEET T-001 INDICATES ALL CODES ARE 2017
 EDITION. PERMIT APPLICATION IS DATED 8/16/2021. PER WPB
 FBC 107.2.1, FLORIDA BUILDING CODES SHALL BE 2020,
 SEVENTH EDITION. N/A; IT IS RECOGNIZED THE PERMIT WAS
 APPLIED FOR PRIOR TO IMPLEMENTATION OF THE 2020 FBC.
  
 6. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE ON THE
 LIFE SAFETY PLANS THE OCCUPANCY GROUP AND OCCUPANCY
 LOAD. THE POOL AREA SHALL BE CONSIDERED. SEE FBC PL
 403.6.
  
 7. SECOND REQUEST: PER WPB FBC 107.2.1 AND 107.3.5.1.3
 PROVIDE
 ...A) MINIMUM PLUMBING FACILITIES
 ...B) FIXTURE REQUIREMENTS
 SEE COMMENT 1
  
 8A. SECOND REQUEST: THE FOLLOWING NOTATIONS ARE MADE ON
 THE PLANS:
 ***A) A-001; NOTE: REMOVE EXISTING HOOD AND ALL KITCHEN
 EQUIPMENT TO ACCOMMODATE NEW EQUIPMENT CONFIGURATION.
 SEE PROPOSED FLOOR PLANS.
 ***B) A-102A; NOTE: KITCHEN DESIGN AND BUFFET AREA BY
 FOOD AND BEVERAGE CONSULTANT. REFER TO SHEET A-102B FOR
 REFERENCE
 ***C)A-101 (PROPOSED FLOOR PLAN) NOTES EXISTING KITCHEN
 PER WPB FBC 107.2.1, PROVIDE CLARIFICATION
  
 8B. SECOND REQUEST: PLAN SHEET A-102B; ENLARGED KITCHEN
 PLAN FOR REFERENCE ONLY: PER WPB FBC 105.1, THE
 APPROPRIATE PLANS AND PERMITS ARE REQUIRED FOR NEW
 EQUIPMENT REQUIRING MECHANICAL, ELECTRICAL, PLUMBING
 (WATER AND DRAIN) OR GAS (SEE COMMENT 8C) CONNECTIONS
 IN THE KITCHEN; THIS INCLUDES REPLACEMENT OF EXISTING
 WITH NEW.
 ***A) PER WPB FBC 107.2.1, REVISE KITCHEN EQUIPMENT
 SCHEDULE TO INDICATING ANY WATER, DRAIN, GAS
 CONNECTIONS AS WELL AS ANY INCLUSIVE OF NEW AND
 EXISTING. NEW EQUIPMENT THAT REQUIRES WATER, DRAIN
 AND/OR GAS (SEE COMMENT 8C) CONNECTIONS SHALL BE
 CLARIFIED, NOTED ON THE SCHEDULE AND DETAILS PROVIDED
 PER WPB FBC 107.2.1. PLANS SHALL INCLUDE ANY PIPING
 INFRASTRUCTURE EXISTING AND NEW REQUIRED TO PROVIDE
 FULL AND ACCURATE INFORMATION (SEE WPB FBC 107.2.1 AND
 107.3.5) AND BE SUBMITTED FOR PLUMBING IN ACCORDANCE
 WITH WPB FBC 107. 3.5.1.3, AND GAS IN ACCORDANCE WITH
 WPB FBC 107.3.5.1.5.
  
 8C. SECOND REQUEST: SEE COMMENT 8B; PLAN SHEET A-102B
 INDICATES TAG 1A DOUBLE OVEN AS NEW. PER WPB FBC
 107.2.1, INDICATE THE ENERGY SOURCE FOR THIS UNIT. IF
 SOURCE IS GAS, A PLAN TO INCLUDE BUT IS NOT LIMITED TO
 SCOPE OF WORK, EQUIPMENT, PIPING, SIZING CALCULATIONS,
 COMBUSTION AIR. THIS INCLUDES EXISTING INFRASTRUCTURE
 AS WELL AS NEW.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  