| 2022-04-12 16:53:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20120964 1301 BELVEDERE RD |
| | |
| | 2ND REVIEW |
| | PLUMBING /GAS COMMENTS: DENIED |
| | THERE WAS NO RESPONSE OR ACKNOWLEDGEMENT OF THE |
| | PLUMBING/GAS COMMENTS FROM REVIEW 1. |
| | |
| | 1.SECOND REQUEST: A SERVICE SINK IS REQUIRED PER FBC PL |
| | TABLE 403.1. |
| | TO BE CLEAR, REFER TO COMMENT 7 BELOW; PROVIDE A |
| | PLUMBING FIXTURE SCHEDULE NOTING REQUIRED PLUMBING |
| | FIXTURES AND QUANTITIES AS REQUIRED BY FBC PL TABLE |
| | 403.1 FOR THE OCCUPANCY (OCCUPANCIES) AND THE ACTUAL |
| | FIXTURES AND QUANTITIES PROVIDED. |
| | |
| | 2. SECOND REQUEST: PROPOSED LOBBY AREA HAS A LARGE |
| | DINING AREA AND PHYSICAL FITNESS ROOM AND APPEARS TO |
| | FIT THE DESCRIPTION FOR ASSEMBLY. PLAN SHEET T-001 |
| | INDICATES R-1 OCCUPANCY. PER WPB FBC 107.2.1, CLARIFY |
| | OCCUPANCY TYPES AND LOADS. |
| | |
| | 3. SECOND REQUEST: PROPOSED SECOND FLOOR IS MADE UP OF |
| | MEETING ROOMS, LOUNGE AREAS AND LECTURE HALLS AND |
| | APPEARS TO FIT THE DESCRIPTION FOR ASSEMBLY. PER WPB |
| | FBC 107.2.1, CLARIFY OCCUPANCY TYPES AND LOADS. |
| | |
| | 4. SECOND REQUEST: PER FBC PL TABLE 403.1 AND FBC ACC |
| | 211.2, PROVIDE DRINKING FOUNTAIN(S) COMPLYING WITH FBC |
| | PL 410.3 AND FBC ACC 602.1 THROUGH 606.7, 305, 306 AND |
| | 307.2. |
| | PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING COMPLIANCE |
| | WITH FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | EXCEPTIONS: |
| | ...A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS |
| | THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE |
| | A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO |
| | BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS. |
| | |
| | 5. N/A-PLAN SHEET T-001 INDICATES ALL CODES ARE 2017 |
| | EDITION. PERMIT APPLICATION IS DATED 8/16/2021. PER WPB |
| | FBC 107.2.1, FLORIDA BUILDING CODES SHALL BE 2020, |
| | SEVENTH EDITION. N/A; IT IS RECOGNIZED THE PERMIT WAS |
| | APPLIED FOR PRIOR TO IMPLEMENTATION OF THE 2020 FBC. |
| | |
| | 6. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE ON THE |
| | LIFE SAFETY PLANS THE OCCUPANCY GROUP AND OCCUPANCY |
| | LOAD. THE POOL AREA SHALL BE CONSIDERED. SEE FBC PL |
| | 403.6. |
| | |
| | 7. SECOND REQUEST: PER WPB FBC 107.2.1 AND 107.3.5.1.3 |
| | PROVIDE |
| | ...A) MINIMUM PLUMBING FACILITIES |
| | ...B) FIXTURE REQUIREMENTS |
| | SEE COMMENT 1 |
| | |
| | 8A. SECOND REQUEST: THE FOLLOWING NOTATIONS ARE MADE ON |
| | THE PLANS: |
| | ***A) A-001; NOTE: REMOVE EXISTING HOOD AND ALL KITCHEN |
| | EQUIPMENT TO ACCOMMODATE NEW EQUIPMENT CONFIGURATION. |
| | SEE PROPOSED FLOOR PLANS. |
| | ***B) A-102A; NOTE: KITCHEN DESIGN AND BUFFET AREA BY |
| | FOOD AND BEVERAGE CONSULTANT. REFER TO SHEET A-102B FOR |
| | REFERENCE |
| | ***C)A-101 (PROPOSED FLOOR PLAN) NOTES EXISTING KITCHEN |
| | PER WPB FBC 107.2.1, PROVIDE CLARIFICATION |
| | |
| | 8B. SECOND REQUEST: PLAN SHEET A-102B; ENLARGED KITCHEN |
| | PLAN FOR REFERENCE ONLY: PER WPB FBC 105.1, THE |
| | APPROPRIATE PLANS AND PERMITS ARE REQUIRED FOR NEW |
| | EQUIPMENT REQUIRING MECHANICAL, ELECTRICAL, PLUMBING |
| | (WATER AND DRAIN) OR GAS (SEE COMMENT 8C) CONNECTIONS |
| | IN THE KITCHEN; THIS INCLUDES REPLACEMENT OF EXISTING |
| | WITH NEW. |
| | ***A) PER WPB FBC 107.2.1, REVISE KITCHEN EQUIPMENT |
| | SCHEDULE TO INDICATING ANY WATER, DRAIN, GAS |
| | CONNECTIONS AS WELL AS ANY INCLUSIVE OF NEW AND |
| | EXISTING. NEW EQUIPMENT THAT REQUIRES WATER, DRAIN |
| | AND/OR GAS (SEE COMMENT 8C) CONNECTIONS SHALL BE |
| | CLARIFIED, NOTED ON THE SCHEDULE AND DETAILS PROVIDED |
| | PER WPB FBC 107.2.1. PLANS SHALL INCLUDE ANY PIPING |
| | INFRASTRUCTURE EXISTING AND NEW REQUIRED TO PROVIDE |
| | FULL AND ACCURATE INFORMATION (SEE WPB FBC 107.2.1 AND |
| | 107.3.5) AND BE SUBMITTED FOR PLUMBING IN ACCORDANCE |
| | WITH WPB FBC 107. 3.5.1.3, AND GAS IN ACCORDANCE WITH |
| | WPB FBC 107.3.5.1.5. |
| | |
| | 8C. SECOND REQUEST: SEE COMMENT 8B; PLAN SHEET A-102B |
| | INDICATES TAG 1A DOUBLE OVEN AS NEW. PER WPB FBC |
| | 107.2.1, INDICATE THE ENERGY SOURCE FOR THIS UNIT. IF |
| | SOURCE IS GAS, A PLAN TO INCLUDE BUT IS NOT LIMITED TO |
| | SCOPE OF WORK, EQUIPMENT, PIPING, SIZING CALCULATIONS, |
| | COMBUSTION AIR. THIS INCLUDES EXISTING INFRASTRUCTURE |
| | AS WELL AS NEW. |
| | |
| | END OF COMMENTS. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE FIRST REVIEW. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |