2021-09-23 13:17:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20120964 1301 BELVEDERE RD
  
 1ST REVIEW
 PLUMBING /GAS COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1.
  
 2. PROPOSED LOBBY AREA HAS A LARGE DINING AREA AND
 PHYSICAL FITNESS ROOM AND APPEARS TO FIT THE
 DESCRIPTION FOR ASSEMBLY. PLAN SHEET T-001 INDICATES
 R-1 OCCUPANCY. PER WPB FBC 107.2.1, CLARIFY OCCUPANCY
 TYPES AND LOADS.
  
 3. PROPOSED SECOND FLOOR IS MADE UP OF MEETING ROOMS,
 LOUNGE AREAS AND LECTURE HALLS AND APPEARS TO FIT THE
 DESCRIPTION FOR ASSEMBLY. PER WPB FBC 107.2.1, CLARIFY
 OCCUPANCY TYPES AND LOADS.
  
 4. PER FBC PL TABLE 403.1 AND FBC ACC 211.2, PROVIDE
 DRINKING FOUNTAIN(S) COMPLYING WITH FBC PL 410.3 AND
 FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2.
 PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING COMPLIANCE
 WITH FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 EXCEPTIONS:
 ...A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS
 THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE
 A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO
 BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS.
  
 5. PLAN SHEET T-001 INDICATES ALL CODES ARE 2017
 EDITION. PERMIT APPLICATION IS DATED 8/16/2021. PER WPB
 FBC 107.2.1, FLORIDA BUILDING CODES SHALL BE 2020,
 SEVENTH EDITION.
  
 6. PER WPB FBC 107.2.1, PROVIDE ON THE LIFE SAFETY
 PLANS THE OCCUPANCY GROUP AND OCCUPANCY LOAD. THE POOL
 AREA SHALL BE CONSIDERED. SEE FBC PL 403.6.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3 PROVIDE
 ...A)MINIMUM PLUMBING FACILITIES
 ...B)FIXTURE REQUIREMENTS
  
 8A.THE FOLLOWING NOTATIONS ARE MADE ON THE PLANS:
 ?A)A-001; NOTE: REMOVE EXISTING HOOD AND ALL KITCHEN
 EQUIPMENT TO ACCOMMODATE NEW EQUIPMENT CONFIGURATION.
 SEE PROPOSED FLOOR PLANS.
 ?B)A-102A; NOTE: KITCHEN DESIGN AND BUFFET AREA BY FOOD
 AND BEVERAGE CONSULTANT. REFER TO SHEET A-102B FOR
 REFERENCE
 ?C)A-101 (PROPOSED FLOOR PLAN) NOTES EXISTING KITCHEN
 PER WPB FBC 107.2.1, PROVIDE CLARIFICATION
  
 8B. PLAN SHEET A-102B; ENLARGED KITCHEN PLAN FOR
 REFERENCE ONLY: PER WPB FBC 105.1, THE APPROPRIATE
 PLANS AND PERMITS ARE REQUIRED FOR NEW EQUIPMENT
 REQUIRING MECHANICAL, ELECTRICAL, PLUMBING (WATER AND
 DRAIN) OR GAS (SEE COMMENT 8C) CONNECTIONS IN THE
 KITCHEN; THIS INCLUDES REPLACEMENT OF EXISTING WITH
 NEW.
 PER WPB FBC 107.2.1, REVISE KITCHEN EQUIPMENT SCHEDULE
 TO INDICATING ANY WATER, DRAIN, GAS CONNECTIONS AS WELL
 AS ANY INCLUSIVE OF NEW AND EXISTING. NEW EQUIPMENT
 THAT REQUIRES WATER, DRAIN AND/OR GAS (SEE COMMENT 8C)
 CONNECTIONS SHALL BE CLARIFIED, NOTED ON THE SCHEDULE
 AND DETAILS PROVIDED PER WPB FBC 107.2.1. PLANS SHALL
 INCLUDE ANY PIPING INFRASTRUCTURE EXISTING AND NEW
 REQUIRED TO PROVIDE FULL AND ACCURATE INFORMATION (SEE
 WPB FBC 107.2.1 AND 107.3.5) AND BE SUBMITTED FOR
 PLUMBING IN ACCORDANCE WITH WPB FBC 107. 3.5.1.3, AND
 GAS IN ACCORDANCE WITH WPB FBC 107.3.5.1.5.
  
 8C. SEE COMMENT 8B; PLAN SHEET A-102B INDICATES TAG 1A
 DOUBLE OVEN AS NEW. PER WPB FBC 107.2.1, INDICATE THE
 ENERGY SOURCE FOR THIS UNIT. IF SOURCE IS GAS, A PLAN
 TO INCLUDE BUT IS NOT LIMITED TO SCOPE OF WORK,
 EQUIPMENT, PIPING, SIZING CALCULATIONS, COMBUSTION AIR.
 THIS INCLUDES EXISTING INFRASTRUCTURE AS WELL AS NEW.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 20120964 1301 BELVEDERE RD
  
  
  
  