Plan Review Notes
Plan Review Notes For Permit 20120919
Permit Number 20120919
Review Stop M
Sequence Number 3
Notes
Date Text
2021-04-30 09:48:041) PLEASE PROVIDE THE MECHANICAL SUB-PERMIT, WITHOUT
 THIS WE CANNOT VERIFY WHO HOLDS THE PERMIT TO DO THE
 INSTALLATION OF THIS MECHANICAL SYSTEM. FS 471.003 (H)
 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST
 ALSO BE SIGNED BY THE MECHANICAL CONTRACTOR OR A
 FLORIDA LICENSED ENGINEER.
 3) THE WALL CAP DETAIL DRAWING ON SHEET M.1 DOES NOT
 MEET CODE FOR A DRYER EXHAUST TERMINATION. FBC RES M
 504.4
 4) PLEASE EXPLAIN HOW THESE UNITS WILL BE VENTILATED.
 FBC M 402,403. PLEASE PROVIDE CALCULATIONS TO SHOW
 VENTILATION CALCLATIONS USING EITHER 402 OR 403.
 5) PLEASE SHOW THE PROTECTION AT THE BATH EXHAUST FAN
 PENETRATION OF THE RATED FLOOR/CEILING ASSEMBLY. FBC M
 607
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER