| Date |
Text |
| 2021-01-04 11:40:34 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120919 |
| | 1/4/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A-3, A-7: REFER TO TABLE 403.1 FBC P: AN |
| | AUTOMATIC WASHING MACHINE HAS BEEN PROVIDED IN |
| | COMPLIANCE WITH THE PLUMBING FIXTURE REQUIREMENTS FOR |
| | R2, HOWEVER IT APPEARS TO BE FOR UNIT C PRIVATE USE AND |
| | NO ACCESS TO THE FIXTURE IS PROVIDED FOR RESIDENTS |
| | UNITS A & B. |
| | |
| | 2) SHEET A-7 PLUMBING RISER- FBC P: |
| | |
| | A) THE WASHING MACHINE DRAIN SHALL NOT CONNECT INTO THE |
| | HORIZONTAL WET VENT OF THE MASTER BATH- SECTION 912.1. |
| | PLEASE REVISE THE ISOMETRIC TO SHOW THE WASHING MACHINE |
| | CONNECTING AT A POINT DOWNSTREAM OD THE WATER CLOSET. |
| | |
| | B) SHOW THE REQUIRED 2? STANDPIPE AND 3? VERTICAL STACK |
| | FOR THE WASHING MACHINE- SECTION 406.2. |
| | |
| | C) SHOW THE MASTER BATH SHOWER DRAIN AND VENT |
| | CONNECTIONS- SECTION 417.3. |
| | |
| | 3) A-7: PROVIDE WATER HEATER EQUIPMENT SCHEDULES |
| | SHOWING MAKES AND MODELS, GALLON SIZES, AND EFFICIENCY |
| | RATINGS- SECTION 502.1 FBC P, AND TABLE C404.2 FBC EC. |
| | PLEASE NOTE THAT MANUFACTURER?S SPECIFICATIONS SHALL BE |
| | SUBMITTED, OR BE ONSITE WITH INSTALLATION MANUALS AT |
| | TIME OF INSPECTION- SECTION 502.1. |
| | |
| | 4) A-3, A-7: SHOW THE WATER HEATER PAN DRAIN RUNS AND |
| | TERMINATION LOCATIONS- SECTIONS 504.7.1 & 504.7.2 FBC |
| | P. |
| | |
| | 5) A-3, A-7: SHOW THE LOCATIONS OF THE SHUTOFF VALVES |
| | TO THE WASHING MACHINE- SECTION 604.10.3 FBC P. |
| | |
| | 6) PROVIDE A WATER RISER AND/OR A WATER SUPPLY PIPING |
| | PLAN- SECTION 107.3.5.1.3(3,13) WPB AMENDMENTS. PLEASE |
| | INCLUDE SYMBOLS TO SHOW LOCATIONS OF SHUTOFF VALVES, |
| | WATER HAMMER ARRESTORS, AND BACKFLOW PREVENTERS- |
| | SECTION 604.9 AND 608.3. |
| | |
| | 7) PROVIDE A SHOWER PAN DETAIL- SECTION 417.5.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |