Plan Review Notes
Plan Review Notes For Permit 20120919
Permit Number 20120919
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-04 11:40:341ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120919
 1/4/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-3, A-7: REFER TO TABLE 403.1 FBC P: AN
 AUTOMATIC WASHING MACHINE HAS BEEN PROVIDED IN
 COMPLIANCE WITH THE PLUMBING FIXTURE REQUIREMENTS FOR
 R2, HOWEVER IT APPEARS TO BE FOR UNIT C PRIVATE USE AND
 NO ACCESS TO THE FIXTURE IS PROVIDED FOR RESIDENTS
 UNITS A & B.
  
 2) SHEET A-7 PLUMBING RISER- FBC P:
  
 A) THE WASHING MACHINE DRAIN SHALL NOT CONNECT INTO THE
 HORIZONTAL WET VENT OF THE MASTER BATH- SECTION 912.1.
 PLEASE REVISE THE ISOMETRIC TO SHOW THE WASHING MACHINE
 CONNECTING AT A POINT DOWNSTREAM OD THE WATER CLOSET.
  
 B) SHOW THE REQUIRED 2? STANDPIPE AND 3? VERTICAL STACK
 FOR THE WASHING MACHINE- SECTION 406.2.
  
 C) SHOW THE MASTER BATH SHOWER DRAIN AND VENT
 CONNECTIONS- SECTION 417.3.
  
 3) A-7: PROVIDE WATER HEATER EQUIPMENT SCHEDULES
 SHOWING MAKES AND MODELS, GALLON SIZES, AND EFFICIENCY
 RATINGS- SECTION 502.1 FBC P, AND TABLE C404.2 FBC EC.
 PLEASE NOTE THAT MANUFACTURER?S SPECIFICATIONS SHALL BE
 SUBMITTED, OR BE ONSITE WITH INSTALLATION MANUALS AT
 TIME OF INSPECTION- SECTION 502.1.
  
 4) A-3, A-7: SHOW THE WATER HEATER PAN DRAIN RUNS AND
 TERMINATION LOCATIONS- SECTIONS 504.7.1 & 504.7.2 FBC
 P.
  
 5) A-3, A-7: SHOW THE LOCATIONS OF THE SHUTOFF VALVES
 TO THE WASHING MACHINE- SECTION 604.10.3 FBC P.
  
 6) PROVIDE A WATER RISER AND/OR A WATER SUPPLY PIPING
 PLAN- SECTION 107.3.5.1.3(3,13) WPB AMENDMENTS. PLEASE
 INCLUDE SYMBOLS TO SHOW LOCATIONS OF SHUTOFF VALVES,
 WATER HAMMER ARRESTORS, AND BACKFLOW PREVENTERS-
 SECTION 604.9 AND 608.3.
  
 7) PROVIDE A SHOWER PAN DETAIL- SECTION 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  