Plan Review Notes
Plan Review Notes For Permit 20120912
Permit Number 20120912
Review Stop B
Sequence Number 2
Notes
Date Text
2021-04-05 08:15:20PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY ADDRESSED. [IN ADDITION TO THE DOOR
 WIDTHS, SPECIFY THE DOOR HEIGHTS ON THE PLANS.] PLEASE
 CLARIFY IF THE TWO DOORS THAT ARE BEING REPLACED ARE
 EXTERIOR DOORS OR INTERIOR DOORS THAT OPEN TO AN
 INTERIOR CORRIDOR. SPECIFY THE SIZES OF THE DOORS ON
 THE PLANS. FBC 107.1.2
  
 2) NOT ADDRESSED. [THIS PROJECT REQUIRES SIGNED AND
 SEALED PLANS FROM A FLORIDA LICENSED DESIGN
 PROFESSIONAL. WORK IS BEING DONE TO THE TENANT
 SEPARATION WALL, THE FLOOR WILL NEED TO BE CORE DRILLED
 FOR THE RELOCATED SINK DRAIN, THE CEILINGS ARE BEING
 FURRED DOWN WHICH MAY AFFECT THE FIRE SPRINKLERS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.] THIS IS A FOUR STORY COMMERCIAL
 BUILDING. IF THE DOORS ARE LOCATED ON THE BUILDINGS
 EXTERIOR, SUBMIT SIGNED AND SEALED COMPONENT AND
 CLADDING PRESSURES FOR THE OPENINGS FROM A FLORIDA
 LICENSED ENGINEER. SUBMIT REQUIRED COMPONENT AND
 CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE
 BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE
 DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE
 ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE
 SUBMITTED. FS 471 & FAC 61G15
  
 3) PARTIALLY ADDRESSED. [THE PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS WERE NOT APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.] FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH EXTERIOR DOOR TYPE. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 4) NOT ADDRESSED. [PROVIDE THE TEST REPORTS FOR THE
 REQUIRED TILE FLOOR SOUND INSULATION.]
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
 -FBC 603.1 FLAME SPREAD - ASTM E 84-09
 -FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) NOT ADDRESSED. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  