| 2021-04-05 08:15:20 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PARTIALLY ADDRESSED. [IN ADDITION TO THE DOOR |
| | WIDTHS, SPECIFY THE DOOR HEIGHTS ON THE PLANS.] PLEASE |
| | CLARIFY IF THE TWO DOORS THAT ARE BEING REPLACED ARE |
| | EXTERIOR DOORS OR INTERIOR DOORS THAT OPEN TO AN |
| | INTERIOR CORRIDOR. SPECIFY THE SIZES OF THE DOORS ON |
| | THE PLANS. FBC 107.1.2 |
| | |
| | 2) NOT ADDRESSED. [THIS PROJECT REQUIRES SIGNED AND |
| | SEALED PLANS FROM A FLORIDA LICENSED DESIGN |
| | PROFESSIONAL. WORK IS BEING DONE TO THE TENANT |
| | SEPARATION WALL, THE FLOOR WILL NEED TO BE CORE DRILLED |
| | FOR THE RELOCATED SINK DRAIN, THE CEILINGS ARE BEING |
| | FURRED DOWN WHICH MAY AFFECT THE FIRE SPRINKLERS. |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE |
| | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 |
| | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA |
| | STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE |
| | SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS |
| | TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN |
| | REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY |
| | ONE SET OF SUBMITTALS.] THIS IS A FOUR STORY COMMERCIAL |
| | BUILDING. IF THE DOORS ARE LOCATED ON THE BUILDINGS |
| | EXTERIOR, SUBMIT SIGNED AND SEALED COMPONENT AND |
| | CLADDING PRESSURES FOR THE OPENINGS FROM A FLORIDA |
| | LICENSED ENGINEER. SUBMIT REQUIRED COMPONENT AND |
| | CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE |
| | BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE |
| | DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE |
| | ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S |
| | ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE |
| | SUBMITTED. FS 471 & FAC 61G15 |
| | |
| | 3) PARTIALLY ADDRESSED. [THE PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS WERE NOT APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD.] FBC 107.3.4 - PROVIDE TWO SETS OF |
| | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH EXTERIOR DOOR TYPE. ONLY ONE SET IS REQUIRED |
| | TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 4) NOT ADDRESSED. [PROVIDE THE TEST REPORTS FOR THE |
| | REQUIRED TILE FLOOR SOUND INSULATION.] |
| | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| | SUBMITTALS: |
| | 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. |
| | > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107. |
| | 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. |
| | 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE, |
| | WOOD, MARBLE, ETC.). |
| | 4. STATED VALUE OF WORK. |
| | 5. DESCRIPTION OF EXISTING SITE CONDITIONS: |
| | (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW |
| | (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ). |
| | 6. PROPOSED UNDERLAYMENT. |
| | 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON |
| | THE EXISTING SITE CONDITIONS. |
| | 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: |
| | E-84, E-90 & E-492. |
| | 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | (UNLESS SUBMITTING ELECTRONICALLY) |
| | -FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| | -FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 5) NOT ADDRESSED. FBC 107.2.1 - INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |