| 2021-01-20 13:58:25 | 01/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET S300, IT SHOWS A SLAB TRENCH DETAIL FOR THE |
| | REPAIR, AND IT SHALL ALSO INCLUDE TERMITE TREATMENT OF |
| | THE SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE |
| | ONSITE FOR A FINAL INSPECTION PER THE 2017 |
| | FBC-RESIDENTIAL SECTION R318.1.1. |
| | |
| | 2. ON SHEET A3.0, THE SERVICE SINK (MOP SINK) |
| | SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE |
| | IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 |
| | AND 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS |
| | SHEET. |
| | |
| | 3. ON SHEET A3.0: |
| | A. PLEASE LABEL ALL ROOMS PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. IN THE SOILED WORKSTATION, IT SHOWS A RADIUS WHICH |
| | IS NOT REQUIRED, PLEASE REMOVE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. IN THE RESTROOM, THE DOOR SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE |
| | PER THE 2017 FBC-ACC SEC. 603.2.3. PLEASE SHOW THE 30" |
| | X 48" AND 60" TRUING RADIUS THE EXCEPTION 2 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. PLEASE SHOW CLEAR FLOOR SPACE IN FRONT OF A SHOWER |
| | OF 36" X 48" PER THE 2017 FBC ACC. SEC. 608.2.1. |
| | |
| | E. THE SINKS IN THE EXAM ROOM SHALL HAVE AT LEAST 5% |
| | AND NOT FEWER THAN ONE OF ACCESSIBILITY PER THE 2017 |
| | FBC ACC. SEC. 212.3. PLEASE SHOW THE SINKS FORWARD |
| | APPROACH PER THE 606.2 CLEAR FLOOR SPACE AND A DETAIL |
| | OF THE SINK ON DETAIL PAGE A 6.1 PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | ON SHEET A6.1; |
| | A. FOR DETAIL 2 OF THE SHOWER, PLEASE SHOW THE |
| | DIMENSION ON THE SIDE VIEW AND LOCATION OF THE GRAB |
| | BARS AND THE CONTROL VALVE PER THE 2017 FBC SEC. |
| | 608.5.1 AND 608.3.1. |
| | |
| | B. PLEASE PROVIDE DETAIL FOR THE BACKING OF THE SHOWER |
| | GRAB BARS AND SEAT PER THE 2017 FBC ACC. SEC. 610.4. |
| | |
| | C. THE GRAB BARS ON THE FLAT TOILET DETAIL NEED THE TO |
| | BE MEASURED FROM CENTERLINE TO CENTERLINE PER THE 207 |
| | FBC AA. SEC. 604.5.2. |
| | |
| | D. ON ADA FIXTURE CLEARANCE, NOTE #1 AND #3 ARE NOT |
| | SHOWN IN BOTH DETAILS PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. ON SHEET 6.2. IN DETAILS 6 AND 7, THE UL HOURLY |
| | RATING IS MISSING. PLEASE DEFINE THE FIREWALL HOUR |
| | RATING PER THE 2017 FBC 714.3. |
| | |
| | 5. ON SHEET 10.1, PLEASE PROVIDE DETAIL CORRESPONDING |
| | WITH A COMMENT 2.E ON THE EXAM ROOM FOR THE CABINET |
| | HEIGHT OF 34? AS PER THE 2017 FBC ACC SEC. 606.3. |
| | |
| | 6. ON SHEET M803, DETAIL MD 6411, A BACKFLOW DEVICE IS |
| | PRESENT, AND IT WILL REQUIRE A SEPARATE PERMIT AS AN |
| | ISOLATION DEVICE WITH THE CERTIFICATION OF A LICENSED |
| | CONTRACTOR. ALL BACKFLOWS THAT ARE ISOLATION MAY BE |
| | COMBINED IN THAT PERMIT, NOT INCLUDING THE CONTAINMENT |
| | BACKFLOW, FIRE DUAL CHECK VALVE, IRRIGATION, AND WATER |
| | SERVICE, WHICH NEED TO BE CERTIFIED BY THE CITY OF WEST |
| | PALM BEACH UTILITIES DEPARTMENT. PLEASE MAKE A NOTE IF |
| | POSSIBLE. PLEASE PROVIDE SEPARATE DRAINS FOR EACH |
| | DEVICE UNLESS DOCUMENTATION IS PROVIDED THAT THE DRAINS |
| | CAN BE COMBINED PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. ON SHEET M804, ON DETAIL MD-0902, A BACKFLOW DEVICE |
| | IS NOT SPECIFIED OR DOES NOT SHOW A DRAIN. PLEASE DO |
| | THE SAME FOR THE COMMENT ABOVE AND PROVIDE THE MAKE AND |
| | MODEL PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. ON SHEET P000, FOR GENERAL PLUMBING NOTES ITEM 10, |
| | THE HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010. |
| | |
| | 9. ON SHEET P100, THERE IS A SANITARY FITTING THAT IS |
| | NOT IN THE FLOW DIRECTION THAT PICKS UP THE MOP SINK ON |
| | ONE SIDE AND TWO SINKS ON THE OTHER SIDE, IN THE PRE-OP |
| | RECOVERY AREA. PLEASE CHANGE PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. NOTE: PLEASE CORRECT ON ISOMETRIC PAGE P600 |
| | AS WELL. THANKS. |
| | |
| | 10. ON SHEET P510; |
| | A. THE CLINICAL SINK/BIDET WATER TEMPERATURE SHALL BE |
| | LIMITED TO A MAXIMUM TEMPERATURE OF 110 F (43 C) BY A |
| | WATER TEMPERATURE LIMITING DEVICE CONFORMING TO ASSE |
| | 1070 OR CSA B125.3 PER THE 2017 FBC P408.3 BIDET WATER |
| | TEMPERATURE. |
| | |
| | B. M-2 AND M-2, EACH WATER STERILIZER FILLED WITH WATER |
| | THROUGH DIRECTLY CONNECTED PIPING SHALL BE EQUIPPED |
| | WITH AN APPROVED LEAKAGE DIVERTER OR BLEED LINE ON THE |
| | WATER SUPPLY CONTROL VALVE TO INDICATE AND CONDUCT ANY |
| | LEAKAGE OF UNSTERILE WATER AWAY FROM THE STERILE ZONE |
| | PER THE 2017 FBC P 609.8 VALVE LEAKAGE DIVERTER. |
| | |
| | C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | 11. ON SHEET P600; |
| | A. PLEASE LABEL ALL THE CLEAN-OUT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. ME-3, ME-2, AND ME-1 COVER HOW THE P-TRAPS ARE |
| | INSTALLED IN THE ISOMETRIC. FOR CLARITY, PLEASE OUTLINE |
| | THE BOXES IN A DASHED FORMAT SO THE P-TRAP CAN BE SEEN |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. PLEASE SHOW LINES TO TRAP PRIMERS ON ALL FLOOR |
| | DRAINS THAT REQUIRE THEM PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON THE GENERAL NOTE C, IT REFERS TO P0.1, AND THERE |
| | IS NO SUCH PAGE. PLEASE CLARIFY THE PAGE NUMBER PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 12. ON SHEET P 601, PLEASE THE INSULATION DETAIL FOR |
| | THE HOT WATER RECIRCULATING SYSTEM PER THE 2017 ENERGY |
| | CODE FBC CE 404.4. |
| | |
| | 13. ON SHEET P801 AND P802, THERE ARE SEVERAL DETAILS |
| | WITH PD-000 IN MULTIPLE USE; PLEASE RELABEL THE DETAIL |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. ON SHEET P801; |
| | A. THE SINGLE TRAP PRIMER DETAIL HAS A VALVE ON THE |
| | RUN. THE TRAP PRIMER NEEDS TO BE ON AN ISOLATION VALVE |
| | FOR MAINTENANCE PLEASE CORRECT PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | B. THE ICE MAKER AND COFFEE MAKER REQUIRES AN INLINE |
| | VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024 |
| | NON-CARBONATED. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |