| Date |
Text |
| 2021-01-20 16:00:44 | 01/20/21 1ST MEDICAL GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. IT IS NOTED ON THE PLAN THE CONTRACTOR AND ANYONE |
| | INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED, |
| | BUT THE INSTALLERS SHALL PROVIDE PROOF FOR PERMIT ISSUE |
| | AND ON THE JOB SITE FOR INSPECTORS APPROVAL PER THE FAC |
| | 61G4-15.031(1)(4A)(4B). |
| | |
| | 2. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION |
| | GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR PER |
| | THE WPB AMEND TO FBC 107.2.1. |
| | |
| | 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION |
| | GUIDES FOR ALL MED GAS EQUIPMENT PER THE WPB AMEND TO |
| | FBC 107.2.1 AND NFPA 99 2015. |
| | |
| | 4. THE CONTRACTOR SHALL PROVE THAT THE QUALIFIER HAS |
| | BEEN BEING CERTIFIED UNDER FLORIDA RULE 61G4 ? 15.031. |
| | |
| | 5 THE INSTALLER SHALL PROVIDE PROOF THAT THE INDIVIDUAL |
| | WORKING ON THE SYSTEM HAS BEEN CERTIFIED PER FLORIDA |
| | RULE 61G4 ? 15.031. |
| | |
| | 6. THE CONTRACTOR SHALL PROVIDE PROOF OF ALL FITTINGS |
| | AND COMPONENTS ARE BEING CLEANED FOR OXYGEN SERVICE PER |
| | THE NFPA 99 2015 SEC. 5.1.10.1.1. |
| | |
| | 7. THE CONTRACTOR SHALL PROVIDE A CERTIFICATION REPORT |
| | SHOWING ALL OUTLETS, VALVES, SOURCE EQUIPMENT ALARMS |
| | PER THE NFPA 99 2015 SEC. 5.1.12.1.1 AND 5.1.12.6. |
| | |
| | 8. ALL MEDICAL GAS TUBING MEETS THE ASTM B 819 |
| | STANDARDS PER THE NFPA 99 2015 SEC. 5.1.10.1. |
| | |
| | 9. THE CONTRACTOR SHALL HAVE PROOF OF RECORDS |
| | AVAILABLE FOR THE FOLLOWING TEST BEING COMPLETED PER |
| | NFPA 99 2015 SEC. 5.1.12.2. |
| | |
| | A. INITIAL PRESSURE TEST (MINIMUM OF 150 PSI) PER THE |
| | NFPA 99 2015 SEC. 5.1.2.2.3.4. |
| | |
| | B. INITIAL CROSS-CONNECT TEST PER THE NFPA 99 2015 SEC. |
| | 5.1.12.2.4. |
| | |
| | C. 24 HOURS STANDING PRESSURE TEST PER THE NFPA 99 2015 |
| | SEC. 5.1.12.2.6.7. |
| | |
| | D. PIPING AND OUTLET PURGE TEST PER THE NFPA 99 2015 |
| | SEC. 5.1.12.2.5. |
| | |
| | E. STANDING VACUUM TEST FOR VACUUM PIPING PER THE NFPA |
| | 99 2015 SEC. 5.1.12.2.7. |
| | |
| | 11. PLEASE SPECIFY WHAT TYPE OF PIPING IS BEING USED |
| | FOR THE COMPRESSED AIR LINES PER THE WPB AMEND TO FBC |
| | 107.2.1. |
| | |
| | 12. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE VACUUM PUMPS AND AIR COMPRESSORS, THE |
| | MUFFLER/INTAKE, THE RECEIVERS, DRYERS, AFTERCOOLERS, |
| | ETC., PER THE WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 13. A PRESSURE INDICATOR(S) SHALL BE LOCATED DOWNSTREAM |
| | OF EACH REGULATOR OR IMMEDIATELY DOWNSTREAM OF THE |
| | REGULATORS' ISOLATING VALVES PER THE NFPA 99 2015 SEC. |
| | 5.1.3.5.5.1 (3). |
| | |
| | 14. PLEASE SHOW THE VACUUM PUMP VENT LINE'S TERMINATION |
| | POINT PER THE NFPA 99 2015 SEC.5.1.3.7.6.2. |
| | |
| | 15. THE VACUUM PUMPS SHALL BE PROVIDED WITH |
| | ANTI-VIBRATION MOUNTINGS PER THE NFPA 99 2015 SEC. |
| | 5.1.3.7.2. |
| | |
| | 16. THE PRESSURE RELIEF VALVES ON THE COMPRESSED AIR |
| | SYSTEM SHALL BE VENTED IN ACCORDANCE WITH NFPA 99 2015 |
| | SEC. 5.1.3.5.6.1 (4). |
| | |
| | 17. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR |
| | COMPRESSOR SHALL BE VENTILATED. HOW IS THIS BEING DONE |
| | PER THE NFPA 99 2015 SECS.5.1.3.3.3.3, 5.1.3.6.3.1, |
| | 5.1.3.7.1.1? |
| | |
| | 18. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM |
| | EXHAUST AND RELIEF PIPING ON THE ROOF PLAN PER THE NFPA |
| | 99 2015 SEC. 5.1.3.7.7, 5.1.3.5.6 |
| | |
| | 19. PROVIDE ROOF DRAWING SHOWING DISTANCE FROM VACUUM |
| | EXHAUST TO AIR INTAKES PER THE WPB AMEND TO FBC |
| | 107.2.1. |
| | |
| | 20. PLEASE SHOWS VACUUM EXHAUST DISCHARGING THROUGH THE |
| | EXTERIOR WALL, AND IT SHALL DISCHARGE THROUGH THE ROOF |
| | PER THE 2017 FBC P 713.6 AND NFPA 99 2015 SEC. |
| | 5.1.3.7.7. |
| | |
| | 21. HOW TO TANK ARE SECURED PER THE WPB AMEND TO FBC |
| | 107.2.1 AND NFPA 99 2015. |
| | |
| | 22. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER |
| | THE WPB AMEND TO FBC 107.2.1 AND NFPA 99 2015. |
| | |
| | 23. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE |
| | WPB AMENDMENTS TO FBC SEC. 105.1. |
| | |
| | 24. PLEASE NOTE THAT TUBING MEETS ASTM B 819 (OXY/MED, |
| | ACR/OXY, ACR/MED) PER THE NFPA 99 23015 SEC. |
| | 5.1.10.1.5. |
| | |
| | 25. PLEASE SUBMIT DETAILS FOR COMPRESSOR SHOWING |
| | COMPLIANCE WITH SECTION NFPA 99 2015 SEC. 5.3.3.5.3. |
| | (1) THRU (17). |
| | |
| | 26. PLEASE ADD A NOTE THAT THE VACUUM SHALL RUN TO A |
| | SLOPE 1/4 "PER TEN FEET TOWARD THE VACUUM PUMP |
| | |
| | 27. PLEASE SHOW THE LIFE SAFETY OF A MED GAS STORAGE |
| | SCHEDULE, AND PLEASE INCLUDE THIS ON THE MED GAS PLAN |
| | SHEETS PER THE WPB AMEND TO FBC 107.2.1. |
| | |
| | PLEASE NOTE THAT SOME COMMENTS MAY NOT APPLY TO THIS |
| | REVIEW, AND A SIMPLE N/A WILL BE SUFFICIENT ON A |
| | RESPONSE. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | NECESSARY PAGES. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION, MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | REFERENCE: NFPA 99 2015 EDITION |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / MEDICAL GAS INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |