| 2021-01-04 15:05:04 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PROVIDE A SURVEY AND A SITE PLAN THAT HAS DIMENSIONS |
| | TO THE PROPERTY LINES AND TO THE BUILDING. 107.2.5 SITE |
| | PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| | APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| | PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| | CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, |
| | FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD |
| | ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| | ACCURATE BOUNDARY LINE SURVEY. |
| | |
| | 2) THE BOUNDARIES OF A SPECIAL FLOOD HAZARD AREA (SFHA) |
| | ENCROACH UPON THIS PROPERTY. SHOW THAT THE GENERATOR IS |
| | NOT LOCATED WITHIN THE BOUNDARIES OF THE SFHA OR SHOW |
| | HOW IT WILL MEET THE REQUIREMENTS OF EQUIPMENT LOCATED |
| | IN A SFHA. FBC 1612 AND CITY OF W.P.B. FLOOD ORDINANCE |
| | |
| | 3) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN |
| | LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16 FOR |
| | THE WALL AND THE GENERATOR. |
| | |
| | 4) THE STRUCTURAL CONNECTION DETAILS ARE NOT SPECIFIC |
| | AS TO QUANTITY AND SPACING OF THE CONNECTORS THAT |
| | ANCHOR THE GENERATOR AND BELLY TANK TO THE SLAB. FBC |
| | 1609 |
| | |
| | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |