| Plan Review Notes For Permit 20120886 |
| Permit Number |
20120886 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-31 12:35:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS A SEPARATION WALL INDICATED CREATING NEW | | | SEPARATE OCCUPANCIES. | | | | | | THE EXISTING AND PROPOSED OTHER OCCUPANCY MAY BE | | | REQUIRED TO HAVE A FIRE RATED SEPARATION WALL. | | | | | | PER NFPA 101, CH 6 | | | | | | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) | | | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, | | | EACH PART OF THE | | | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED | | | IN THIS CHAPTER, | | | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY | | | FIRE-RESISTIVE | | | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, | | | TABLE 6.1.14.4.1(A), | | | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED | | | BY APPROVED | | | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY | | | 6.1.14.4.6. | | | | | | PLEASE REVIEW AND PROIVDE APPLICABLE OCCUPANCIES AND | | | ANY REQUIRED LISTED RATED WALL ASSEMBLY. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|