Plan Review Notes
Plan Review Notes For Permit 20120868
Permit Number 20120868
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-29 17:58:1912/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE ADDRESS COMMENT SEVEN ON THE BUILDING REVIEW
 TO COMPLY 2017 FBC ACCESSIBILITY CODE.
  
 2. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 3. PLEASE PROVIDE THE LAVATORY KNEE AND TOE CLEARANCES
 PER THE 2017 FBC ACC SEC. 306.1 TOE CLEARANCE.
  
 4. PROVIDE CABINET DETAIL SHOWING THE SINK AND OR LAVS
 HEIGHT OF 34" INCHES MAXIMUM PER THE 2017 FBC ACC SEC.
 606.3.
  
 5. PLEASE SHOW THE DRINKING FOUNTAINS AND SHOW THE
 ACCESSIBILITY IN ACCORDANCE WITH 2017 FBC ACC SEC.
 211.2 & 602.1- 602.6. PROVIDE DRAWINGS AND DETAILS
 SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE DRINKING
 FOUNTAIN 2017 FBC ACC SEC. 602.2 CLEAR FLOOR SPACE AND
 PLEASE SHOW KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 SPOUT LOCATIONS PER THE 2017 FBC ACC SEC. 306, 307, &
 602.2, COMPLIANCE WITH 2017 FBC ACC SEC. 307.2
 PROTRUSION LIMITS.
  
 6. ON SHEET P2.0;
  
 A. THE IN THE ISOMETRIC, THE DRINKING FOUNTAIN AND MOP
 SINK ARE SHOWN ON A DISCHARGING ON A WET VENT. PLEASE
 SHOW DOWNSTREAM OF THE BATHROOM GROUP PER THE 2017 FBC
 SEC. P 912.1.
  
 B. PLEASE SHOW ON THE WATER RISER FOR THE LAVS THAT THE
 TEMPERING VALVES SHALL CONFORM TO ASSE 1070 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. PLEASE SHOW ON THE ISOMETRIC THE SHOW LOCATION AND
 TYPE OF MAIN SHUTOFF 2017 FBC SEC. P 606.1.
  
 7. ON SHEET C1;
 A. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING, AND
 ACCESSIBILITY REFERENCED USED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 101.4 REFERENCED CODES.
  
 B. PROJECT INDEX IS MISSING P2.0; PLEASE PROVIDE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. PLEASE PROVIDE A SLAB REPAIR DETAIL AND SHOW THE
 REPAIR'S WIDTH, THE MINIMUM THICKNESS OF THE CONCRETE
 TO BE REPLACED, AND THE CONCRETE'S PSI. SHOW THE
 DOWELS' SIZE AND LENGTH, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, AND THE DOWELS' SPACING IN THE
 CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AND THE REQUIRED VAPOR BARRIER OVER THE
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved