2020-12-18 12:38:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 1 - THERE IS AN INDICATION OF A MIXED USE
 OCCUPANCY; HOWEVER, THERE IS NO INDICATIONS OF
 SEPARATIONS
  
 PER NFPA 101, CH 6
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 SHEET E 2.0 INDICATES A SHOWROOM WHICH CAN BE
 CONSIDERED MERCANTILE, NFPA 101, CH 36, NEW MERCANTILE
 OCCUPANCIES, AND THE PROPOSED SHALL COMPLY WITH THIS
 OCCUPANCY AS IT IS THE MOST RESTRICTIVE.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED
 INFORMATIONAL NARRATIVE OF THE OCCUPANCY TYPE FOR
 CONSIDERATION.
  
  
  
 2) THERE IS NO LIFE SAFETY PLAN INDICATING OCCUPANCY
 LOADS, TRAVEL DISTANCES, TRAVEL PATHS, EXIT WIDTH, EXIT
 CAPACITY, ETC.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) THERE ARE NO STAIR & HANDRAIL DETAILS.
  
 36.2.2.3 STAIRS.
 36.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE WITH
 NFPA 101, CH 36 & 7
  
  
  
 4) PLEASE PROVIDE DETAILS OF WHAT THE SHOWROOM WILL
 CONSIST OF, PRODUCT, EQUIPMENT, SHELVEING, PRPOSED
 FLOOR PLAN.....
  
  
  
 5) THERE IS ONLY ONE EXIT FROM INDICATED FROM THE 2ND
 FL.
  
 PER NFPA 101, CH 36
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 36.1.2.2 SUBCLASSIFICATION OF OCCUPANCY.
 36.1.2.2.1 MERCANTILE OCCUPANCIES SHALL BE
 SUBCLASSIFIED AS
 FOLLOWS:
  
 (3) CLASS C, ALL MERCANTILE OCCUPANCIES OF NOT MORE
 THAN 3000
 FT2 (280 M2) GROSS AREA AND USED FOR SALES PURPOSES
 OCCUPYING ONE STORY ONLY
  
 IF THIS OCCUPACNY IS MIXED, NONSEPARATED IT IS NOT A
 CLASS C 2 EXITS ARE REQUIRED.
  
  
  
 6) THERE IS NO EXIT DOOR HARDWARE INDICATED.
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 7) SHEET E 1.0 - THERE IS AN EXISTING DOOR AT THE
 PROPOSED LOBBY CONNECTING THE EXISTING STORAGE. THE
 DOOR IS MARKED WITH AN EXIT SIGN FROM THE STORAGE
 LEADING THRU THE LOBBY. THE DOOR IS INDICATED AS
 SWINGING AGAINST EGRESS.
  
 THOUGH EXISTING THIS DOOR IS REQUIRED TO SWING IN
 DIRECTION OF EGRESS PER CH 38 & CH 7
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL