| 2020-12-29 14:28:16 | INTERIOR RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE CLARIFY EXISTING VERSES NEW - MEP DRAWINGS | | | SHOW 2ND FLOOR AS OFFICE AND SHOW ROOM (MERCANTILE) - | | | ARCHITECTURAL DRAWINGS SHOW 2ND FLOOR AS ALL STORAGE. | | | 2) OCCUPANT LOAD AND MEANS OF EGRESS WILL BE REVIEWED | | | AFTER CLARIFICATION - PLEASE UP DATE OCCUPANT LOAD AND | | | MEANS OF EGRESS FOR THE OCCUPANCY CLASSIFICATION. | | | 3) SHOW THE TOTAL TRAVEL DISTANCE FROM THE 2ND FLOOR TO | | | THE EXIT. FBC 1017.3 | | | 4) PLEASE SHOW THE OCCUPANT LOAD FOR EACH ROOM FBC | | | 1004.1.2 | | | 5) PLEASE SHOW THE STAIR HEADROOM CLEARANCE TO COMPLY | | | WITH FBC 1011.3 | | | 6) DRAWING A1.0 SAYS TO REMOVE THE STEEL JOIST - I DO | | | NOT SEE THE STRUCTURAL DRAWINGS THAT SHOW THE REMOVAL | | | AND FIX. | | | 7) PLEASE SHOW ALL RESTROOM ACCESSIBILITY DETAILS - | | | GRAB BAR SIZES AND HEIGHT, MIRROR HEIGHT, PAPER | | | DISPENSER LOCATIONS, ETC. TO SHOW COMPLIANCE WITH FBC | | | ACCESSIBILITY. |
|