Plan Review Notes
Plan Review Notes For Permit 20120862
Permit Number 20120862
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-18 15:18:1412/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM ITS
 PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEAT PUMP, AND FILTER. ALL SYSTEM COMPONENTS EXCEPT THE
 PUMP.
  
 2. IDENTIFY THE PUMP CURVE, WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. IT IS NEEDED
 TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE HEAT PUMP PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 A. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF
 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2,
 STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A
 TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED
 TO VERIFY PROCEDURE COMPLIANCE PER THE 2017 FBC-ENERGY
 ? SEC. R 403.10.5
  
 4. A PERMIT IS REQUIRED FOR BACKFLOW (PVB) ON THE
 AUTOFILL PER THE 2017 FBC-PLUMBING SEC.608.1.
  
 5. NOTE: A REDUCED PRESSURE ZONE ASSEMBLY IS REQUIRED
 SINCE AN AUTO-FILL IS PRESENT PER THE CITY OF WEST PALM
 BEACH ORD #2853-95. A PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES BEFORE
 FINAL INSPECTION. PLEASE CONTACT THE CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. A
 BACKFLOW PRESSURE VACUUM BREAKER IS REQUIRED WITH A
 PERMIT ON THE AUTOFILL BY A LICENSED CONTRACTOR AND
 MUST BE CERTIFIED PER THE 2017 FBC-PLUMBING SEC.608.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  