| 2020-12-29 13:17:39 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE UPDATED LOAD CALC'S. |
| | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | |
| | 2. PROVIDE EQUIPMENT SERVICE OUTLET. |
| | E3901.12 |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | 3. GFCI PROTECTION REQUIRED. |
| | E4203.1.3GFCI PROTECTION. |
| | ALL 15- AND 20-AMPERE, SINGLE PHASE, 125-VOLT |
| | RECEPTACLES LOCATED WITHIN 20 FEET (6096 MM) OF THE |
| | INSIDE WALLS OF POOLS AND OUTDOOR SPAS AND HOT TUBS |
| | SHALL BE PROTECTED BY A GROUND-FAULT CIRCUIT |
| | INTERRUPTER. OUTLETS SUPPLYING POOL PUMP MOTORS |
| | SUPPLIED FROM BRANCH CIRCUITS RATED AT 120 VOLTS |
| | THROUGH 240 VOLTS, SINGLE PHASE, WHETHER BY RECEPTACLE |
| | OR DIRECT CONNECTION, SHALL BE PROVIDED WITH |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. [680.21(C) AND 680.22(A)(4)] |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |