| 2020-12-22 14:14:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LA 2.10 - THERE ARE INDICATIONS OF A FIREPIT; |
| | HOWEVER, THERE ARE NO DETAILS. |
| | |
| | PLEASE PROVIDE DETAILS REGARDING WHAT THE DEFINITION OF |
| | "FIRE MEDIA" & "FIRE BOX" ARE? |
| | |
| | THERE SHALL BE DETERANTS IN PLACE TO PROTECT AGAINST |
| | ACCIDENTAL/INTENTIONAL FLAME CONTACT. |
| | |
| | WHAT IS THE PROPOSED DIMENSION FROM THE TOP OF ANY |
| | VIEWING PANE TO THE TOP OF THE FLAME?( PREVENT REACHING |
| | OVER TO MAKE FLAME CONTACT) |
| | |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF FUEL SUPPLY FOR THE |
| | FIREPIT. |
| | |
| | PLEASE PROVIDE DETAILS, AS WELL AS, A MANUFACTURER'S |
| | SPEC SHEET FOR REVIEW. |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF AN EMERGENCY SHUTOFF FOR |
| | THE FUEL SUPPLY. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF FUEL SUPPLY FOR THE |
| | GRILLS. |
| | |
| | PLEASE PROVIDE DETAILS, AS WELL AS, A MANUFACTURER'S |
| | SPEC SHEET FOR REVIEW. |
| | |
| | |
| | 4A) SHEET LA 1.10 - THERE IS AN INDICATION OF GRILL |
| | LOCATED NEAR AN AREA OF TREES AND AN OUTLINE OF A |
| | BUILDING. |
| | |
| | WHAT ARE THE DIMENSIONS TO THESE OBJECTS? |
| | |
| | 10.10.6 COOKING EQUIPMENT. |
| | 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, |
| | NO |
| | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR |
| | COOKING, HEATING, |
| | OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY |
| | BALCONY, |
| | UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF |
| | ANY |
| | STRUCTURE. |
| | |
| | THE OPERATION OF A GRILL WILL PRODUCE SMOKE/VAPORS THAT |
| | MAY ENTER AREA APARTMENTS WITH APPLICABLE COMPLAINTS. |
| | |
| | WHAT IS THE PROPOSED REMEDY SHOULD THIS OCCUR? |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 5) THERE ARE NO FIRE EXTINGUISHERS INDICATED NEAR THE |
| | FIREPIT NOR THE BBQ GRILLS. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |