2021-01-05 15:04:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) ELECTRICAL SCOPE OF WORK IS NOT CLEAR. THE NARRATIVE
 PROVIDED MENTIONS THAT "THIS PLAN AND SCOPE OF WORK
 WILL BE PERFORMED UNDER BUILDING PERMIT FOR PORTOFINO
 PLACE??. MASTER PERMIT NUMBER #17120809 PER SHEET
 E0.10". AND THEN THE NARRATIVE SAYS UNDER A) THAT THIS
 PROPOSAL INCLUDES LIGHTING FIXTURES AND SOME CHARGING
 STATIONS.
  
 AFTER CHECKING E0.10 (PERMIT 17120809) IT SEEMS THAT
 THE ELECTRICAL WORK FOR POOL LIGHTING AND CHARGING
 STATIONS WAS NOT INCLUDED THEN AND THE ELECTRICAL
 APPROVED WAS FOR THE CLUBHOUSE.
  
 PLEASE CLARIFY. IF ELECTRICAL WORK IS BEING DONE THAT
 WAS NOT INCLUDED ON PERMIT 17120809 PLEASE PROVIDE
 ELECTRICAL DRAWINGS SHOWING CIRCUITS, WIRE AND BREAKER
 SIZES, PANELS SCHEDULES AFFECTED, LOCATION OF CHARGING
 STATIONS. THE LIGHTING DETAILS SHEET (LA2.40) ONLY
 PROVIDES SPECS ON FIXTURES AND CHARGING STATIONS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  