| 2021-01-05 15:04:49 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. |
| | |
| | 1) ELECTRICAL SCOPE OF WORK IS NOT CLEAR. THE NARRATIVE |
| | PROVIDED MENTIONS THAT "THIS PLAN AND SCOPE OF WORK |
| | WILL BE PERFORMED UNDER BUILDING PERMIT FOR PORTOFINO |
| | PLACE??. MASTER PERMIT NUMBER #17120809 PER SHEET |
| | E0.10". AND THEN THE NARRATIVE SAYS UNDER A) THAT THIS |
| | PROPOSAL INCLUDES LIGHTING FIXTURES AND SOME CHARGING |
| | STATIONS. |
| | |
| | AFTER CHECKING E0.10 (PERMIT 17120809) IT SEEMS THAT |
| | THE ELECTRICAL WORK FOR POOL LIGHTING AND CHARGING |
| | STATIONS WAS NOT INCLUDED THEN AND THE ELECTRICAL |
| | APPROVED WAS FOR THE CLUBHOUSE. |
| | |
| | PLEASE CLARIFY. IF ELECTRICAL WORK IS BEING DONE THAT |
| | WAS NOT INCLUDED ON PERMIT 17120809 PLEASE PROVIDE |
| | ELECTRICAL DRAWINGS SHOWING CIRCUITS, WIRE AND BREAKER |
| | SIZES, PANELS SCHEDULES AFFECTED, LOCATION OF CHARGING |
| | STATIONS. THE LIGHTING DETAILS SHEET (LA2.40) ONLY |
| | PROVIDES SPECS ON FIXTURES AND CHARGING STATIONS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |