Plan Review Notes
Plan Review Notes For Permit 20120841
Permit Number 20120841
Review Stop G
Sequence Number 3
Notes
Date Text
2021-03-22 14:52:0803/22/21 3RD GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. MOST TANK-LESS UNITS CALL FOR A 10.5" WATER COLUMN.
 THE SERVICE METER DISCHARGES IS A TWO PSI REQUIRING A
 REGULATOR FOR THIS UNIT AS PER THE MANUFACTURER'S
 SPECIFICATION. THE LAST COMMENT SAID, ?TANKLESS WATER
 HEATER HAS A GAS APPLIANCE REGULATOR BUILT-IN.? THERE
 WAS NO DOCUMENTATION SUPPORTING THAT. PLEASE PROVIDE
 ALL THE INFORMATION BELOW TO COMPLETE THIS REVIEW.
  
 2. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC.
 G2421.1.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. A NOTE ON PLANS THE LOCATION OF ONE THE TANK-LESS
 WATER HEATER WAS PLACED, AND THE OTHER TANLESS LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER IS NOT SHOWN. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. THRID REQUEST, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT (RANGE, TANKLESS, GENERATOR, AND POLL HEATER)
 TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  