| Date |
Text |
| 2021-02-23 13:15:53 | 02/23/21 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. MOST TANK-LESS UNITS CALL FOR A 10.5" WATER COLUMN. |
| | THE SERVICE METER DISCHARGES IS A TWO PSI REQUIRING A |
| | REGULATOR FOR THIS UNIT AS PER THE MANUFACTURER'S |
| | SPECIFICATION. THE LAST COMMENT SAID, ?TANKLESS WATER |
| | HEATER HAS A GAS APPLIANCE REGULATOR BUILT-IN.? THERE |
| | WAS NO DOCUMENTATION SUPPORTING THAT. PLEASE PROVIDE |
| | ALL THE INFORMATION BELOW TO COMPLETE THIS REVIEW. |
| | |
| | 2. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| | FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC. |
| | G2421.1. |
| | |
| | 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 4. A NOTE ON PLANS THE LOCATION OF ONE THE TANK-LESS |
| | WATER HEATER WAS PLACED, AND THE OTHER TANLESS LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER IS NOT SHOWN. THE LOCATION |
| | OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. SECOND REQUEST, PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT (RANGE, TANKLESS, GENERATOR, AND POLL HEATER) |
| | TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |