| 2020-12-30 13:30:00 | 12/30/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P-3, THE ISOMETRIC DRAWING HAS SIGNAGE FOR |
| | EMERGENCY SHUT-OFF, WHICH IS NOT ON THE PLAN, AND NO |
| | REFERENCE CODE WAS CALLED OUT IN A.01. YOU MAY REMOVE |
| | IT OR CLARIFY ISOMETRIC AND CODE REFERENCE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE EXPOSED GAS PIPING NOTE IS NOT REQUIRED FOR |
| | RESIDENTIAL USE. YOU MAY CHOOSE TO LEAVE IT THERE OR |
| | REMOVE IT. |
| | |
| | 3. MOST TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. |
| | |
| | 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | |
| | 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 6. PLEASE NOTE ON PLANS THE LOCATION OF THE TANK-LESS |
| | WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 7. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| | (RANGE, TANKLESS, GENERATOR, AND POLL HEATER) TO VERIFY |
| | COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 8. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 9. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1" OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| | G2421.2. |
| | |
| | 10. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |