| Plan Review Notes For Permit 20120841 |
| Permit Number |
20120841 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-30 15:40:26 | PLAN REVIEW / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2014 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE ELECTRICAL LEGEND. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. SMOKE ALARM REQUIRED OUTSIDE BEDROOM #3. | | | R314.3 LOCATION. | | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | 1. IN EACH SLEEPING ROOM. | | | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | 3. OUTLET REQUIRED AT SGD IN ART STUDIO. | | | E3901.2.1 SPACING. | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE | | | OUTLET. [210.52(A)(1)] | | | | | | | | | | | 2020-12-30 14:30:20 | ADDED LOW VOLTAGE REVIEW. CT |
|