| Date |
Text |
| 2021-02-17 13:50:01 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | ELECTRICAL REVIEW STATUS: FAILED, SAME COMMENTS AS |
| | REVIEW #1. |
| | |
| | 1) DRAWINGS SHOW THREE A/C UNITS, BUT PANEL SCHEDULE |
| | ONLY SHOWS ONE UNIT. PLEASE CLARIFY AND CORRECT. FBC |
| | 107 |
| | 2) AHU SPECS INDICATE A10KW HEATER, BUT LOAD |
| | CALCULATIONS AND PANEL SCHEDULE SHOW AN 8.6 KW LOAD. |
| | PLEASE CLARIFY AND CORRECT. FBC 107 |
| | 3) PLEASE INDICATE CIRCUIT NUMBERS FOR ALL A/C |
| | EQUIPMENT ON POWER PLANS AND MATCH THEM TO PANEL |
| | SCHEDULE. FBC 107 |
| | 4) REVISION #3 INCLUDES THREE PIECES OF EQUIPMENT (H#1, |
| | H#2, AND H#3). PLEASE CLARIFY WHAT THEY ARE AND INCLUDE |
| | THEM ON YOUR SYMBOLS OR NOTES. IF PART OF THE A/C |
| | UNITS, PLEASE INDICATE CIRCUITS FEEDING THEM AND |
| | INCLUDE ON PANEL SCHEDULE. FBC 107 |
| | 5) A GFI, WP RECEPTABLE BE REQUIRED ON BACK OF UNIT. |
| | NEC 210.52 |
| | 6) PLEASE SEE SIGNATURE COMMENTS |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |