| Plan Review Notes For Permit 20120805 |
| Permit Number |
20120805 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-12-22 13:23:50 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE FLAT ROOF | | | ASSEMBLY THAT IS HI-LIGHTED IS -45 PSF. THIS IS NOT | | | ADEQUATE FOR THIS PROJECT. SUBMIT SIGNED AND SEALED RAS | | | 117 CALCULATIONS FOR ENHANCED FASTENING PER GENERAL | | | LIMITATION #7 OF THE PRODUCT APPROVAL. FBC R301 | | | | | | 2) THE SCOPE OF WORK HAS BEEN INCREASED BY ADDING THE | | | FLAT ROOF AREA, HOWEVER, THE VALUE FOR THE PROJECT WAS | | | NOT INCREASED. SUBMIT A COPY OF THE CONTRACT WITH THE | | | COSTS OF THE WORK. FBC 109 |
|