| Plan Review Notes For Permit 20120803 |
| Permit Number |
20120803 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2021-11-30 14:07:26 | 5TH REVIEW FBC-2020 MECHANICAL | | | PERMIT-20120803 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M7.1: PLEASE PROVIDE THE OUTDOOR AIR | | | CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATIONS | | | FROM 2020FBC M TABLE 403.3.1.1 AND CODE SECTION | | | 403.3.1.1. THE VENTILATION CALCULATIONS SEEM TO BE A | | | MIX BETWEEN FBC M TABLE 403.3.1.1 AND ASHRAE 62.1-2013. | | | PLEASE REMOVE ALL PARTS NOT ASSOCIATED WITH FBC M | | | 403.3.1.1 AS YOU CANNOT MIX BOTH CALCULATIONS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|