| Plan Review Notes For Permit 20120803 |
| Permit Number |
20120803 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-09-21 07:09:10 | 4TH REVIEW FBC-2020 MECHANICAL | | | PERMIT-20120803 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | THE MECHANICAL REVIEW COULD NOT BE COMPLETED AS THE | | | REVISED SHEETS BELOW WERE NOT SUBMITTED. | | | | | | 1) THE REVISED SHEET LOADED UNDER SHEET M2.1.1 IS | | | ACTUALLY SHEET M2.1. PLEASE SUBMIT A REVISED SHEET | | | M2.1.1. | | | | | | 2) REVISED SHEET M7.1 HAS NOT BEEN SUBMITTED TO SHOW | | | THE VENTILATION CALCULATIONS THAT WERE REQUESTED. | | | | | | 3) REVISED SHEET M8.1 WAS NOT SUBMITTED TO SHOW THE | | | DETAIL FOR THE INTAKE AIR. | | | | | | 4) REVISED SHEETS M4.1, M4.2 WERE NOT SUBMITTED IN THIS | | | CYCLE. | | | | | | 5) THERE IS NO SHEET M4.3 | | | | | | | | | PLAN REVIEW RESULTS: DENIED. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|