| 2021-10-04 06:44:29 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT-20120803 |
| | 10/4/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE |
| | PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER |
| | THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| | MANUAL. |
| | 2) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY |
| | WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE |
| | WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25 |
| | FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL |
| | COMPLY WITH SEC, 4.19.2.2. |
| | 4) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY |
| | DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON |
| | AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER |
| | TABLE 403.1 OF THE FBC-PLUMBING. |
| | 5) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL THE |
| | TOILET STALLS IN THE COMMON AREA TOILET ROOMS. COMPLY |
| | WITH FBC-PLUMBING SEC.405.3.1. |
| | 6) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S |
| | RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING |
| | SEC.403.6 & TABLE 403.6. |
| | 7) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI |
| | A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER |
| | TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1 |
| | SEC.4.25. |
| | 8) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE |
| | DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO |
| | THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI |
| | A117.1 SEC. 4.16, 4.17 & FIGURE 228. |
| | 9) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN. |
| | COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF |
| | ANSI A117.1 SEC.4.16.2. |
| | 10) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS |
| | SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| | BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF |
| | THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE |
| | 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE |
| | CENTERLINE OF THE BAR. |
| | 11) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE |
| | DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS |
| | PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29. |
| | 12) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE |
| | PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER |
| | FBC-PLUMBING SEC.417.5.2. |
| | 13) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR |
| | EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS |
| | USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 14) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES |
| | THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A |
| | MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43. |
| | 15) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS |
| | WILL COMPLY WITH ANSI A117.1 - 1986. |
| | 16) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND |
| | A-10.4. CLARIFY. |
| | 17) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE |
| | CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A |
| | 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING |
| | OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM |
| | PER FHADM PAGE 7.39. |
| | 18) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET |
| | AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME. |
| | CLARIFY. |
| | 19) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO |
| | SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN |
| | SUBMITTED WITH THESE PLANS. CLARIFY. |
| | 20) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL |
| | DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 21) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT |
| | APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND |
| | RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1, |
| | MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL |
| | ROOM.CLARIFY. |
| | 22) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2. |
| | THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5. |
| | CLARIFY. |
| | 23) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND |
| | LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION |
| | OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 24) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT |
| | APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND |
| | RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1, |
| | B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A |
| | RISER IN STAIR #2. THIS IS NOT PERMITTED PER |
| | FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO |
| | OCCUR ON ALL LEVELS. CLARIFY. |
| | 25) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR |
| | PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 26) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3 |
| | AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON |
| | SHT. A-2.1. CLARIFY. |
| | 27) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO |
| | MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2 |
| | INCH WATER SUPPLY BRANCH. CLARIFY. |
| | 28) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD |
| | NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY. |
| | 29) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS |
| | ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1, |
| | NOT P-4.2. CLARIFY. |
| | 30) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES |
| | CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED |
| | MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE |
| | STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A |
| | RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK |
| | VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER |
| | FBC-PLUMBING SEC. 918.3.1. |
| | 31) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES |
| | CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED |
| | MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE |
| | STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A |
| | RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK |
| | VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER |
| | FBC-PLUMBING SEC. 918.3.1. |
| | 32) SHT. P-5.2 - SANITARY AND WATER RISERS - |
| | IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM |
| | NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 33) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY |
| | DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE |
| | MANUFACTURER'S INFORMATION AND THE APPROVED LISTING |
| | NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1. |
| | 34) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A |
| | RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD |
| | INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE |
| | FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL |
| | 723. |
| | 35) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE |
| | DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY |
| | SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE |
| | SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5) |
| | UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING. |
| | 36) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND |
| | TABLE 308.5. |
| | 37) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL |
| | SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS, |
| | ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 38) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED |
| | PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED |
| | ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING |
| | 608.13.2. |
| | 39) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE |
| | PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE |
| | LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC. |
| | 606.3. |
| | 40) SUBMIT SANITARY AND WATER RISERS FOR ALL THE COMMON |
| | AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB AMEND. TO |
| | FBC SEC. 107.3.5.1.3. |
| | 41) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS SHALL |
| | BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING |
| | SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE |
| | 1024. |
| | 42) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER |
| | SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER |
| | SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. |
| | 43) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER |
| | DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A |
| | BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING |
| | VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER |
| | PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL |
| | BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR |
| | REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR |
| | REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER |
| | FBC SECS.604.8, 604.8.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |