| 2021-09-30 12:32:02 | NEW 8 STORY APT AND 6 STORY PARKING GARAGE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE ROOM "USE" FOR THE ROOMS MARKED |
| | G105, G104, G102, 167 ON THE FLOOR PLAN. |
| | |
| | 2) PLEASE REVISE THE LIFE SAFETY PLANS - TO MATCH THE |
| | REVISED FLOOR PLANS PROVIDED. |
| | |
| | 3) BUILDING IS NOT CONSIDERED A HIGHRISE - UNIT MARKED |
| | ST-1 AND ST-1 MOD - THE SLEEPING ROOM REQUIRES AN |
| | EMERGENCY EXIT. FBC 1030.1 |
| | |
| | 4) CAR CHARGING STATIONS FOR THE PARKING ARE SHOWN ON |
| | THE ELECTRICAL DRAWINGS BUT NOT ON THE ARCHITECTURAL |
| | FLOOR PLAN. ELECTRIC VEHICLE CHARGING STATIONS ARE |
| | BEING INSTALLED - PLEASE SHOW THAT AT LEAST 1 OF THE |
| | CHARGING STATIONS IS A MARKED ACCESSIBLE PARKING SPACE, |
| | ACCESS AISLE, SIGNAGE ETC. ALLOWING ACCESS TO THE |
| | CHARGER - PER FBC 502 |
| | |
| | 5) ARCHITECT NEEDS TO SPECIFY HOW THE WALLS BETWEEN |
| | UNITS AND SERVICE OR CORRIDOR AREA MEET THE |
| | REQUIREMENTS OF FBC 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. PENETRATIONS OR |
| | OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING; |
| | ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS; |
| | SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL |
| | BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO |
| | MAINTAIN THE REQUIRED RATINGS. |
| | |
| | 6) THE ONLY CALCULATIONS FOR THE OPEN GARAGE |
| | VENTILATION PROVIDE ARE FOR THE 1ST FLOOR - THE |
| | PERCENTAGES ARE NOT SHOWN. PLEASE PROVIDE THE |
| | CALCULATIONS FOR THE OPEN GARAGE PER FBC 406.5.2 FOR |
| | NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF THE |
| | STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS ON |
| | TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN |
| | EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| | PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| | THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE |
| | PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 |
| | PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS |
| | SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY |
| | DISTRIBUTED OPENINGS. |
| | |
| | 7) DRAWING A-4.8 - THE FINISH SCHEDULE NEEDS TO SHOW |
| | THE COMMON RESTROOM WALL FINISH TO COMPLY WITH (DRYWALL |
| | IS NOT CONSIDERED A HARD SURFACE) 1210.2.2 WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. |
| | |
| | 8) DRAWING A-4.8 CANNOT HAVE A WOOD BASEBOARD IN THE |
| | COMMON RESTROOMS - FBC 1210.2.1 FLOORS AND WALL BASES. |
| | IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| | SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| | FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| | WALLS NOT LESS THAN 4 INCHES (102 MM). |
| | |
| | |
| | |
| | |
| | |
| | |
| | |