| 2021-03-04 18:48:13 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT-20120803 |
| | 3/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1- THIS BUILDING WAS DESIGNED UNDER THE REQUIREMENTS OF |
| | THE FAIR HOUSING ACT. INDICATE ON THE PLAN IN EACH UNIT |
| | WHICH DESIGN SPECIFICATION ("A" OR "B" OF THE ACT) WAS |
| | USED IN THE DESIGN OF THE UNITS. |
| | |
| | 2- THE WASHING MACHINE VALVES SHALL BE ACCESSIBLE |
| | WITHOUT MOVING THE UNIT PER THE 2017 FBC SEC. P 606.3 |
| | |
| | 3- THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS. WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4- NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE |
| | PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 |
| | THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH 602.7. PER FBCACC SEC. 211.2 & FBC-PLUMBING SEC. |
| | 410.3. |
| | |
| | 5- ON PAGE A2.1.2 RR A-110 & RR A-109 WHERE PLUMBING |
| | FIXTURES ARE REQUIRED, SEPARATE FACILITIES SHALL BE |
| | PROVIDED FOR EACH SEX. PER FBC P 403.2 |
| | |
| | 6- ON PAGE A2.1.2 B1 UNITS DO NOT SHOW THE LAVATORIES |
| | OR THE WATER CLOSETS ON THE FLOOR PLAN |
| | |
| | 7- ON PAGE A2.1.2 ASSE 1022 BACKFLOWS ARE REQUIRED FOR |
| | THE BISTRO BAR ICE MAKER AND DISHWASHER |
| | |
| | 8- AN OUTSIDE SHOWER IS REQUIRED FOR THE POOL AREA |
| | |
| | 9- PLEASE PROVIDE A DETAIL OF WHAT WILL BE INSTALLED IN |
| | THE DOG SPA |
| | |
| | 10- REDUCED PRESSURE PRINCIPAL BACKFLOW PREVENTER IS |
| | REQUIRED FOR THE TRASH CHUTE WATER LINE THAT COMPLIES |
| | WITH FBCP 608.13.2 |
| | |
| | 11- ON PLAN PAGE A4.3 UNIT B1- PLEASE CLARIFY |
| | TUB/SHOWER? INDICATED IN THE SHOWER |
| | |
| | 12- ON PLAN PAGE A4.9 DETAIL 7 & 8 UNIT B2 IS NOT A |
| | BATHROOM |
| | |
| | 13- ON PLAN A5.1 IN THE WOMENS RESTROOM A-119 CLEAR |
| | FLOOR SPACE SHALL NOT IMPEDE ON THE WATER CLOSET 5' |
| | CLEAR FLOOR SPACE |
| | |
| | 14- ON PLAN A5.1 BOH ROOM A-120 . PROVIDE ELEVATION ON |
| | THE CABINETRY AND SINK LOCATION |
| | |
| | 15- ON PLAN A5.1 POWDER ROOM A-111 RESTROOMS INDICATE |
| | THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | |
| | 16- ON PLAN A5.4 DETAIL NUMBER 2. PLEASE INDICATE THE |
| | INTERIOR DIMENTIONS OF THE ACCESSIBLE RESTOOMS & IN THE |
| | WOMENS RESTROOM A-119 CLEAR FLOOR SPACE SHALL NOT |
| | IMPEDE ON THE WATER CLOSET 5' CLEAR FLOOR SPACE |
| | |
| | 17- PROVIDE SPECIFICATIONS ON THE ROOF DRAINS THAT WILL |
| | BE INSTALLED |
| | |
| | 18- ON PAGE 256-P5.1 AAV'S ARE NOT ALLOWED TO BE |
| | INSTALLED ON THE 1ST- 4TH FLOORS PER FBCP 918.3.1 WHERE |
| | THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. |
| | |
| | 19- WATER METERS : THERE IS NO INFORMATION ON THE SPECS |
| | SHOWING THE FLAME SPREAD INDEX AND SMOKE-DEVELOPED |
| | INDEX OF THE UNIT. IT MUST COMPLY WITH T SEC.602.2.1 OF |
| | THE MECHANICAL CODE AND COMPLY WITH THE TESTING |
| | CRITERIA IN ASTM E84 OR UL 723. |
| | |
| | 20- ON PLAN PAGE A5.4 DETAIL 1 THE 5 FOOT WATER CLOSET |
| | CLEAR FLOOR SPACE SHALL NOT HAVE ANY OTHER PLUMBING |
| | FIXTURES INSIDE OF THAT 5 FOOT CLEAR FLOOR SPACE. THE |
| | URINAL SHALL BE RELOCATED. PLEASE SHOW THE CLEAR FLOOR |
| | SPACE FOR ALL OF THE ACCESSIBLE PLUMBING FIXTURES IN |
| | THE MEN'S AND WOMEN'S RESTROOMS. |
| | |
| | 21- ON PLAN PAGE A5.4 DETAIL 2,3,4,5,8,9,10,11,12,14 |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 22- ON PLAN PAGE A5.4 DETAIL 1 & 2 BOTH DETAILS |
| | INDICATE "POOL ACCESS/ PAVILLION LEVEL 1. PLEASE |
| | CLARIFY WHICH DETAIL IS FOR THE POOL ACCESS PAVILLION |
| | AND WHICH DETAIL IS FOR THE RESTROOM. |
| | |
| | 23. PER FBCACC 2017 603.3 MIRRORS. A SINGLE FULL-LENGTH |
| | MIRROR CAN ACCOMMODATE A GREATER NUMBER OF PEOPLE, |
| | INCLUDING CHILDREN. IN ORDER FOR MIRRORS TO BE USABLE |
| | BY PEOPLE WHO ARE AMBULATORY AND PEOPLE WHO USE |
| | WHEELCHAIRS, THE TOP EDGE OF MIRRORS SHOULD BE 74 |
| | INCHES (1880 MM) MINIMUM FROM THE FLOOR OR GROUND |
| | |
| | 24- GRAB BARS ON A5.4 THE SIDE WALL GRAB BAR SHALL BE |
| | 42 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES |
| | (305 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 |
| | INCHES (1370 MM) MINIMUM FROM THE REAR WALL. THE REAR |
| | WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM |
| | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610 |
| | MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 25. ON PAGE A5.4 TOILET PAPER DISPENSERS SHALL COMPLY |
| | WITH 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 |
| | INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM |
| | AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR |
| | AND SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS |
| | SHALL NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT |
| | DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 26. ON PAGE A5.4 IF SOAP AND TOWEL DISPENSERS ARE |
| | PROVIDED, THEY MUST BE LOCATED WITHIN THE REACH RANGES |
| | SPECIFIED IN 308. LOCATE SOAP AND TOWEL DISPENSERS SO |
| | THAT THEY ARE CONVENIENTLY USABLE BY A PERSON AT THE |
| | ACCESSIBLE LAVATORY. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |