| 2021-02-09 15:43:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) NEED TO SHOW A ONLINE DIAGRAM OF THE SERVICES AND |
| | HOW THIS WILL WORK IN THE BUILDING. |
| | |
| | 2) I DON'T SEE AN EMERGENCY SYSTEM? LIGHTS, FIRE PUMP, |
| | ELEVATORS??? |
| | |
| | 3) PLEASE PROVIDE AN ELECTRICAL ROOM LAYOUT FOR EACH |
| | ELECTRICAL ROOM. |
| | |
| | 4) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| | ALARM SYSTEM. PAGE E-5.2 |
| | |
| | 5) MOST SERVICE MAINS WILL BE REQUIRED TO COMPLY WITH |
| | 240.87 PLEASE INDICATE HOW THIS WILL BE ACOMPLISHED. |
| | |
| | 6) NEED TO SHOW FAULT CURRENT CALCULATIONS FOR THE |
| | MAINS AND SUB PANELS PER 110.9, 110.10 PAGES E-5.1, |
| | E-5.2, AND NOTED ON THE PLAN FOR THE SIGNAGE NEEDED PER |
| | 110.24. |
| | |
| | 7) HOW ARE THE GOUPING OF THE SERVICE MAINS THAT DON'T |
| | MEET EXCEPTIONS HP1A, HP3B, AMENITY, FIRE PUMP. |
| | |
| | 8) FIRE PUMP SHOWS ONLY FPL FPL IS NOT A RELIABLE |
| | SOURCE OF POWER PER 695.3 |
| | |
| | 9) GARAGE CIRCUITS SHALL COME FROM ONE SOURCE ONLY |
| | CAN'T TELL IF ALL CIRCUITS COME FROM SAME SOURCE PAGES |
| | E-2.1--E-2.6 |
| | |
| | 10) IF YOU ARE SUPPLYING SHUNT TRIPS TO THE FIRE COMAND |
| | CENTER HOW ARE THE OTHER NON-SHUNTED SREVICES GOING TO |
| | COMPLY WITH A SAFE SYSTEM? |
| | |
| | 11) SMOKE ALARMS IN UNITS NEED TO BE ADJUSTED TO MEET |
| | THE REQUIREMENTS OF NFPA 72 WITH REFERENCE TO LOCATION |
| | TO BATHROOMS, AND KITCHEN COOKING APPLIANCES. |
| | |
| | 12) SIGNAGE AND DIRECTORIES NEEDED TO BE INSTALLED FOR |
| | THE SERVICE LOCATIONS THROUGHOUT THE BUILDING WILL NEED |
| | TO BE SUBMITTED FOR REVIEW BY THE FIRE DEPTARTMENT. |
| | PLEASE INSERT A PAGE INTO THE ELECTRICAL DRAWINGS FOR |
| | REVIEW. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |