| Plan Review Notes For Permit 20120790 |
| Permit Number |
20120790 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-04-29 17:32:26 | 2ND REVIEW FBC-2020 RES. FUEL GAS | | | PERMIT- 20120790 | | | 4/29/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED RISER SHOWS A NATURAL GAS SYSTEM HOWEVER | | | THE NOTES ON THE RISER INDICATE THE AN LP SYSTEM | | | SUPPLIED BY AN 500-GALLON LP TANK- PLEASE CORRECT THE | | | NOTES AND THE LP PIPE SIZING TABLES SHOWN. | | | | | | 2) 2ND REQUEST TO PROVIDE THE TOTAL LOAD OF THE SYSTEM | | | AND THE TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE | | | METER TO THE MOST REMOTE OUTLET- SECTIONS G2413.2 & | | | G2413.4.1 FBC RES. | | | | | | 3) PROVIDE THE SIZE OF THE MAIN SUPPLY PIPE FROM THE | | | METER TO THE TEE- SECTION G2413.2 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|