| 2021-04-09 17:34:38 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 20120790 |
| | 4/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: PLEASE UPDATE THE FBC- 2017 CODE |
| | REFERENCES. THE FBC -2020 7TH EDITION CODES WENT INTO |
| | EFFECT ON 12/31/2020. |
| | |
| | 2) GAS RISER: PLEASE ADD THE BBQ GRILL TO THE RISER |
| | THAT WAS INSTALLED UNDER PERMIT- 13020828- SECTION |
| | G2413.2 FBC RES. |
| | |
| | 3) PLEASE PROVIDE THE TOTAL BTU LOAD OF THE SYSTEM AND |
| | THE TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER |
| | TO MOST REMOTE OUTLET- SECTION G2413.4.1 FBC RES. |
| | |
| | 4) SUBMIT UPDATED GENERATOR SPECS. THE SPECS SUBMITTED |
| | ARE OUTDATED AND SHOW AN INCORRECT BTU LOAD FOR THE |
| | GENERATOR- SECTION G2447.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |