Plan Review Notes
Plan Review Notes For Permit 20120790
Permit Number 20120790
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-09 17:34:381ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 20120790
 4/9/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: PLEASE UPDATE THE FBC- 2017 CODE
 REFERENCES. THE FBC -2020 7TH EDITION CODES WENT INTO
 EFFECT ON 12/31/2020.
  
 2) GAS RISER: PLEASE ADD THE BBQ GRILL TO THE RISER
 THAT WAS INSTALLED UNDER PERMIT- 13020828- SECTION
 G2413.2 FBC RES.
  
 3) PLEASE PROVIDE THE TOTAL BTU LOAD OF THE SYSTEM AND
 THE TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER
 TO MOST REMOTE OUTLET- SECTION G2413.4.1 FBC RES.
  
 4) SUBMIT UPDATED GENERATOR SPECS. THE SPECS SUBMITTED
 ARE OUTDATED AND SHOW AN INCORRECT BTU LOAD FOR THE
 GENERATOR- SECTION G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  