Plan Review Notes
Plan Review Notes For Permit 20120783
Permit Number 20120783
Review Stop M
Sequence Number 1
Notes
Date Text
2021-02-02 09:51:42PLAN DENIED
 1) REFER TO SECTION M1602.2 RETURN AIR OPENINGS # 4.
 2020 RESIDENTIAL CODE. ( RETURN AIR SHALL NOT BE TAKEN
 FROM A CLOSET.
 2) PROVIDE CFM ON ALL SUPPLY DROPS.
 SECTION 107 FBC.
 3) PROVIDE A VALUE OF WORK ON THE APPLICATION.
 4) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS
 ALL INFORMATION,DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 FBC 2020.