| Date |
Text |
| 2021-01-09 19:36:20 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT-20120755 |
| | 1/9/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND |
| | THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| | ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A |
| | PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL |
| | CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES |
| | SECS. G2413.4.1, G2413.4.2. |
| | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4) TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| | 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| | 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS |
| | SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| | THROUGH 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413. |
| | 7) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| | FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413.4.1. |
| | 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017 |
| | FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | 9) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017 |
| | FBC FUEL GAS RES. SEC. G2413.2. |
| | 10) SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| | 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | 11) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL |
| | GAS RES. SEC. G2413.3 |
| | 12) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| | FUEL GAS RES. SEC. G2421.1. |
| | 13) THE PLANS AND DOCCUMENTS SUBMITTED ARE ILLEGIBLE. |
| | SUBMIT A COPY OF CLEAR AND LEGIBLE PLANS FOR REVIEW. |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 14) THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING |
| | PERMITS VALUATIONS. |
| | 15) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| | IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| | REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| | BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| | ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS |
| | 16) SHOW THE LOCATION OF ALL OPERABLE WINDOWS AND DOORS |
| | ON THE PLAN AND THE DISTANCE OF THE TANKLESS WATER |
| | HEATER FROM EACH. WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 17) THE ADDRESS OF PROJECT OR RESIDENCE MUST BE ON |
| | PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | 18) SEPERATE PERMIT REQUIRED FOR PLUMBING PORTION OF |
| | THE TANKLESS HEATER INSTALLATION |
| | 19) SEPERATE ELECTRICAL PERMIT REQUIRED FOR THE |
| | INSTALLATION OF A TANKLESS HEATER |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |
| | |
| | |