| 2020-12-29 08:07:36 | ATM | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ATM IS SUBJECT TO WIND LOADS - PLEASE SHOW THE WIND | | | DESIGN CRITERIA USED FOR DESIGN - 2017 FBC 1603.1 | | | 2) PLEASE SHOW THE ANCHORAGE OF THE ATM TO THE | | | FOUNDATION - ANCHOR TYPE, SIZE AND AMOUNT. | | | 3) PLEASE SHOW THE ACCESSIBLE PATH FROM THE ACCESSIBLE | | | PARKING SPACE TO THE ACCESSIBLE ATM TO COMPLY WITH FBC | | | 402 | | | |
|