| Plan Review Notes For Permit 20120722 |
| Permit Number |
20120722 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-29 10:17:47 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. SUBMITTED MIAMI-DADE COUNTY NOA 19-0311.04 COVERS | | | MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(8). ALL | | | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. | | | ENGINEERED SIGNED AND SEALED CALCULATIONS MAY BE | | | REQUIRED. | | | 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF | | | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING | | | CLEARLY IDENTIFIED ON DRAWING. | | | |
|