| 2021-03-09 12:06:02 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20120717 |
| | 3/9/21 |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH NOTES ADDED FOR FURTHER CLARIFICATION |
| | 1) FAILED. GAS RISER: THE RESUBMITTED GAS RISER IS NOT |
| | LEGIBLE. THE PRINT AND DETAILS ARE TOO FAINT TO READ. |
| | PLEASE RESUBMIT A CLEAR COPY WITH EMBOLDENED PRINT FOR |
| | REVIEW AND FOR PUBLIC RECORD SCANNING- SECTION 107.2.1 |
| | WPB. |
| | A) PROVIDE THE SIZE OF THE PIPE FROM THE METER TO THE |
| | 1ST AND 2ND TEES- G2413.4.1 FBC RES. |
| | B) PROVIDE THE SIZE OF THE PIPE DROP FROM THE 2ND TEE |
| | TO THE LOW PRESSURE REGULATOR, AND THE BRANCH PIPE |
| | SIZES FROM THE REGULATOR TO THE WATER HEATER, DRYER AND |
| | RANGE- G2413.4.1 & G2413.4.2. |
| | C) PROVIDE THE TOTAL GAS LOAD OF THE SYSTEM AND THE |
| | TOTAL DEVELOPED LENGTH FROM THE METER TO THE MOST |
| | REMOTE OUTLET- G2413.1, G2413.2, & G2413.4.1. |
| | 2) FAILED. THE TANKLESS WATER HEATER, BBQ, FIREPLACE, |
| | AND POOL HEATER WERE NOT INCLUDED IN THE MASTER PERMIT- |
| | 20071263. PLEASE PROVIDE THE FOLLOWING ITEMS: THE SPECS |
| | FOR THE BBQ GRILL AND FIREPIT WERE NOT SUBMITTED. |
| | PLEASE DO NOT SUBMIT ENTIRE INSTALLATION MANUALS- THOSE |
| | CAN BE ONSITE. SUBMIT ONLY THE MANUFACTURER?S |
| | SPECIFICATIONS SHEETS WHICH ARE TYPICALLY ONE OR TWO |
| | DATA SHEETS THAT SHOW COMPLIANCE STANDARDS AND LISTING |
| | NUMBERS, BTUH CAPACITIES AND INPUT PRESSURES. |
| | A) FAILED. MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | HEATER, BBQ GRILL, FIREPLACE, AND POOL HEATER- |
| | SECTIONS- G2408.1 & G2448.1. SEE NOTES UNDER ITEM 2 |
| | ABOVE. |
| | C) FAILED. ADJUST THE $2000.00 VALUE ON THE APPLICATION |
| | TO INCLUDE THE COST OF THE NEW APPLIANCES- SECTION |
| | 109.3 WPB. NO INCREASE IN VALUE OR DOCUMENTATION |
| | PROVIDED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |