| 2021-05-11 12:45:43 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20120712 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-7.2: THE FITNESS AREA SHOULD BE CALCULATED |
| | WITH THE AEROBICS COLUMN OF TABLE 403.3.1.1. THE |
| | OUTDOOR AIR CALCULATIONS SHOULD BE BASED ON 403.3.1.1 |
| | AND TABLE 403.3.1.1 NOT ON THE ARCHITECTURAL OCCUPANT |
| | COUNT. |
| | |
| | 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE |
| | OCCUPANCY CLASSIFICATION FROM TABLE 403.3.1.1 EXAMPLE- |
| | LOUNGE, PLEASE MAKE SURE I CAN LOOK AT WHAT YOU ARE |
| | LOOKING AT WITH THE CALCULATIONS. LOUNGE IS UNDER FOOD |
| | AND BEVERAGE SERVICE, IF I DO THE MATH I GET A LOT MORE |
| | OUTDOOR AIR CFMS THAT WHAT IS SHOWN IN THE AHU-4 CHART. |
| | |
| | 3) PLEASE USE ONE METHOD FOR CALCULATING OUTDOOR AIR |
| | EITHER TABLE 403.3.1.1 OR AN APPROVED ENGINEERING |
| | ANALYSIS. FBC M 403.3.1.1 THE OCCUPANT LOAD UTILIZED |
| | FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE NOT LESS |
| | THAN THE NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM |
| | OCCUPANT LOAD RATE INDICATED IN TABLE 403.3.1.1. |
| | VENTILATION RATES FOR OCCUPANCIES NOT REPRESENTED IN |
| | TABLE 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY |
| | CLASSIFICATION THAT IS MOST SIMILAR IN TERMS OF |
| | OCCUPANT DENSITY, ACTIVITIES AND BUILDING CONSTRUCTION; |
| | OR SHALL BE DETERMINED BY AN APPROVED ENGINEERING |
| | ANALYSIS. |
| | |
| | 4) SHEET M-2.3B, M-2.5B, M-2.7B, IS SHOWING A PLAN KEY |
| | NOTE 15 BUT THERE IS NO KEY NOTE 15 SHOWN ON THE |
| | DRAWING. PLEASE INCLUDE THE KEY NOTE 15 COMMENTS. FBC M |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |