| Plan Review Notes For Permit 20120712 |
| Permit Number |
20120712 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-07-21 14:53:31 | 1) SHTS. P-2.0A, P-2.0B & P-2.0C - THE GAS LINE APPEARS | | | LIKE IT MAY BE RUNNING UNDER THE BUILDING IN CERTAIN | | | AREAS. PE PIPE CAN ONLY BE INSTALLED OUTSIDE, | | | UNDERGROUND. CLARIFY THIS ON THE AFOREMENTIONED | | | SHEETS.FBC-FUEL GAS SEC.404.17.1. A YELLOW INSULATED | | | COPPER TRACER WIRE OR OTHER APPROVED CONDUCTOR OR | | | PRODUCT SHALL BE INSTALLED ADJACENT TO UNDERGROUND | | | NONMETALLIC PIPING. FBC-FUEL GAS SECTION 404.17.3. | | | 2) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER | | | FBC-FUEL GAS SEC. 301.3. THE SUBMITTED DOCUMENTS FOR | | | THE TAVOOLA 4 FIRE TABLE DOES NOT SHOW IT IS LISTED OR | | | LABELED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|