| Plan Review Notes For Permit 20120712 |
| Permit Number |
20120712 |
|
| Review Stop |
P-GREASE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-22 15:00:21 | 1) THE CONCRETE GREASE INTERCEPTORS SHALL COMPLY WITH | | | CITY OF WEST PALM BEACH STANDARD DRAWING GS-7. CONTACT | | | THE CITY OF WEST PALM BEACH ENGINEERING DEPT. AT | | | 561-494-1079 OR 561-835-7423 FOR A COPY OF THE DRAWING. | | | THE SUBMITTED DETAILS DO NOT APPEAR TO COMPLY WITH THE | | | CITY STANDARD DRAWING GS-7. | | | 2) SHT. P-2.0A - A SAMPLING PORT IS REQUIRED ON THE | | | OUTLET OF GI-2. THE SAMPLING PORT ON THE INLET OF GI- 1 | | | IS NOT SERVING ANY PURPOSE. | | | 3) SHT. P-2.0B - THE PLAN SHOWS THE GI-3 INTERCEPTOR | | | AND LABELS IT AS A GREASE INTERCEPTOR YET THIS ITEM IS | | | LABELED AS OI-1 ON SHT. P-6.3. SHT. P-0.1 ALSO CALLS | | | THIS OUT AS AN OIL INTERCEPTOR AND A GREASE | | | INTERCEPTOR.CLARIFY. NOTE: A GREASE INTERCEPTOR CANNOT | | | BE UTILIZED AS AN OIL INTERCEPTOR. CLARIFY AS TO WHAT | | | THIS RECEPTACLE IS TO BE USED FOR. SHT. P-2.0B ALSO | | | CALLS THIS OUT AS GI-3. CLARIFY.SUBMIT A DETAIL OF THE | | | OIL INTERCEPTOR IF THAT IS WHAT IT IS. IF IT IS A | | | GREASE INTERCEPTOR, SUBMIT DETAILS OF THE INTERCEPTOR. | | | FBC SEC. 107.3.5.1.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|