| 2021-03-15 11:04:33 | 1) SHT. C2.4 - PLACE A NOTE ON THE PLAN THAT SEPARATE |
| | PERMITS ARE REQUIRED FOR THE IRRIGATION, DOMESTIC |
| | WATER, AND FIRE LINE BACKFLOWS PER THE CITY OF WEST |
| | PALM BEACH CROSS-CONNECTION CONTROL MANUAL. |
| | 2) SUBMIT A PLUMBING FIXTURE COUNT SCHEDULE FOR THE |
| | MINIMUM NUMBER OF REQUIRED SANITARY FACILITIES REQUIRED |
| | FOR EACH OCCUPANCY TYPE AT THE POOL, AREA FITNESS |
| | CENTER, PAVILION/GAMING/WET BAR, MULTIPURPOSE |
| | LAWN/AMPHITHEATER,FIRE PIT AREA, AND ALL OTHER COMMON |
| | AREAS LOCATED ON LEVEL ONE. COMPLY WITH FBC-PLUMBING |
| | TABLE 403.1. |
| | 3) SHT. LS-0.0 - NOTE #2 (A) REFERS TO SHT P-6.1 FOR |
| | LISTED UL ASSEMBLIES FOR THROUGH PENETRATION FIRE STOP |
| | SYSTEMS. THERE IS NO FIRE STOP INFORMATION ON SHT. |
| | P-6.1. CLARIFY. |
| | 4) SHTS. A-2.1, A-5.2, & A-5.9 - THE DOOR IN THE MEN'S |
| | TOILET ROOM #A-0125 CANNOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR THE LAVATORY. COMPLY WITH |
| | FBC-ACCESS. SEC.603.2.3. SEE EXCEPTION #2. SHOW THE 30 |
| | INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR SPACE |
| | LOCATED BEYOND THE THE ARC OF THE DOOR ON THE PLANS. |
| | 5) SHTS. A-2.1, A-5.2, & A-5.9 - THE DOOR IN ONE OF THE |
| | WOMEN'S TOILET ROOMS #A-0126 CANNOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR THE WATER CLOSET. COMPLY |
| | WITH FBC-ACCESS. SEC.603.2.3. SEE EXCEPTION #2. SHOW |
| | THE 30 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR |
| | SPACE LOCATED BEYOND THE THE ARC OF THE DOOR ON THE |
| | PLANS. |
| | 6) SHT. A-5.2 & A=5.10 - THE SINK IN THE HOSPITALITY |
| | AREA (A-0109) AND LOUNGE AREA ( A-0121) SHALL COMPLY |
| | WITH ANSI A117.1 - 1986. |
| | 7) THE SINK |
| | 8) SHT. SP-1 SHOWS A DOG PARK.INDICATE ON THE PLAN IF |
| | THERE ARE ANY PLUMBING FIXTURES LOCATED IN THIS AREA |
| | AND IF SO, SUPPLY A WATER AND SANITARY RISER. WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.3. THERE IS ALSO A SQUARE |
| | MARKED "TX." CLARIFY WAHT THIS ITEM IS AND IT'S USE. |
| | THE PLAN STATES "SEE CIVIL" BUT THERE IS NO INFORMATION |
| | ON THE CIVIL DRAWINGS. CLARIFY. |
| | 9) SHTS. A-4.1 & A-4.2 - SHOW THE DEPTH OF THE |
| | LAVATORIES ADJACENT TO THE WATER CLOSETS IN THE |
| | ADAPTABLE BATHROOMS. THE LAVATORIES SHALL HAVE A |
| | MAXIMUM DEPTH OF 24 INCHES PER THE FAIR HOUSING ACT |
| | DESIGN MANUAL PAGE 7.43. |
| | 10) SHT. A-4 - UNITS B1 & B1-MOD - SHOW THE LENGTH OF |
| | THE TUB AND SHOWER WALL NEXT TO THE WATER CLOSET. THE |
| | WALL LENGTH SHALL NOT EXCEED 24 INCHES PER THE FHA |
| | DESIGN MANUAL PAGE 7.44. |
| | 11) SHT. A-5.3 - MEN'S RESTROOM A-0130B - THE URINAL |
| | CANNOT BE LOCATED INSIDE THE CLEAR FLOOR SPACE FOR THE |
| | URINAL. ANSI A117.1 - 1986 SEC.4.16, FIGURE 28. |
| | 12) SHT. A-5.3 - FIXTURE MOUNTING HEIGHTS SHOWS A GRAB |
| | BAR IN THE VERTICAL POSITION. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION. THERE IS NO |
| | EXCEPTION IN THE ANSI STANDARD FOR VERTICAL GRAB BARS. |
| | ANSI A117.1-1986 SEC.4.16.4. |
| | 13) SHT. A-5.3 - POOL RESTROOM ELEVATION DRAWINGS - THE |
| | HEIGHT OF THE GRAB BARS IS MEASURED TO THE BOTTOM OF |
| | THE GRAB BAR. SEC. 4.16.4 & FIGURE 29 (A) (B) OF ANSI |
| | A117.1-1986 REQUIRE THE GRAB BARS TO BE MEASURED TO THE |
| | CENTERLINE OF THE GRAB BAR.CLARIFY. |
| | 14) SHT. A-5.3 - POOL RESTROOM ELEVATION DRAWINGS - |
| | SHOW THE LOCATION OF THE GRAB BARS FROM THE SIDE WALL |
| | AND REAR WALL OF THE WATER CLOSET ON THE DRAWINGS AND |
| | SHOW THE LENGTH OF THE GRAB BARS PER ANSI A117.1 SEC. |
| | 4.16.4. |
| | 15) SHT. A-5.3 - THE PLAN SHOWS THE CENTERLINE OF THE |
| | WATER CLOSET 1 FOOT 8 INCHES FROM THE SIDE WALL TO THE |
| | CENTERLINE OF THE WATER CLOSET. THE WATER CLOSET SHALL |
| | BE LOCATED 18 INCHES TO THE CENTERLINE FROM THE SIDE |
| | WALL. ANSI A117.1 SEC.4.16.2. SHOW THE DIMENSION FROM |
| | THE FINISHED SURFACE OF THE WALL. |
| | 16) SHT. A-5.3 - FIXTURE MOUNTING HEIGHTS - THE GRAB |
| | BARS ARE SHOWN MEASURED TO THE CENTERLINE OF THE GRAB |
| | BARS BUT THE NOTE STATES "TOP OF GRIPPING SURFACE." THE |
| | GRAB BARS SHALL BE MEESURED TO THE CENTERLINE PER ANSI |
| | A117.1 SEC.4.16.4. REMOVE THE NOTE. |
| | 17) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE CLEAR |
| | FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES IN |
| | THE COMMON AREA TOILET ROOMS AND TOILET STALLS. COMPLY |
| | WITH ANSI A117.1. SECS. 4.15 THOUGH 4.21. |
| | 18) SHT. A-5.5 - CLARIFY THE WALL SUBSTRATE AND FINISH |
| | AROUND THE MOP SINK. THE FINISH SCHEDULE NOTES "1 COAT |
| | PRIMER AND 2 COATS PAINT". THE WALL FFINISH SHALL |
| | COMPLY WITH FBC-BUILDING SEC. 1210.2.2.DRYWALL AND |
| | EPOXY PAINT DOES NOT COMPLY.NOTE #16 REFERS TO INTERIOR |
| | DESIGNER'S DRAWINGS BUT THERE ARE NO SUCH DRAWINGS IN |
| | THIS SUBMITTAL. CLARIFY. |
| | 19) SHT. A-5.7. - MAINTENANCE RESTROOM DETAILS #1 & #2 |
| | APPEAR TO SHOW THE GRAB BARS MEASURED TO THE BOTTOM OF |
| | THE GRAB BAR. GRAB BARS SHALL BE MEASURED TO THE |
| | CENTERLINE OF THE GRAB BAR PER ANSI A117.1 SEC.4.16.4. |
| | 20) SHT. A-5.7 - DETAILS #1 & #2 - THERE IS NO GRAB BAR |
| | SHOWN ON THE SIDE ADJACENT TO THE WATER CLOSET. |
| | CLARIFY. COMPLY WITH ANSI A117.1 SEC.4.16.4. |
| | 21) SHT. A-5.7 - SHOW THE WIDTH OF THE TOILET ROOM. |
| | THERE IS NO DIMENSION SHOWN ON THE PLAN. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 22) SHT. A-5.9 - AMENITY RESTROOMS - DETAILS #1,2,6,7,8 |
| | & 9 APPEAR TO SHOW THE GRAB BARS MEASURED TO THE BOTTOM |
| | OF THE GRAB BAR. GRAB BARS SHALL BE MEASURED TO THE |
| | CENTERLINE PER ANSI A117.1 SEC.4.16.4. RFERENCE IS ALSO |
| | MADE TO I.D. DRAWINGS BUT THERE ARE NO I.D. DRAWINGS IN |
| | THIS SUBMITTAL. |
| | 23) SHT. A-5.9 - AMENITY RESTROOMS - THERE ARE |
| | ADDITIONAL ELEVATION DETAILS SHOWING THE GRAB BARS |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE WITH NOTES |
| | STATING SUCH. GRAB BARS SHALL BE MEASURED TO THE |
| | CENTERLINE PER ANSI A117.1 SEC.4.16.4.REMOVE THE NOTE |
| | REFERRING TO THE TOP OF THE GRIPPING SURFACE. |
| | 24) SHT. A-5.9 - SHOW THE LOCATION OF THE GRAB BARS |
| | FROM THE SIDE WALL AND REAR WALL OF THE WATER CLOSET ON |
| | THE DRAWINGS AND SHOW THE LENGTH OF THE GRAB BARS PER |
| | ANSI A117.1 SEC. 4.16.4.25) |
| | 25) SHT. A-5.9 - A VERTICAL GRAB BAR IS SHOWN ON THE |
| | SIDE WALL NEXT TO THE WATER CLOSET IN THE ELEVATION |
| | DETAILS ON THE BOTTOM RIGHT SIDE OF THE PLAN.GRAB BARS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION. THERE IS |
| | NO EXCEPTION IN THE ANSI STANDARD FOR VERTICAL GRAB |
| | BARS. ANSI A117.1-1986 SEC.4.16.4 |
| | 26) SHT. A-5.9 - HANDICAP MOUNTING HEIGHT DETAILS - THE |
| | REAR GRAB BAR AT THE WATER CLOSET SHOWS A DIMENSION OF |
| | 3 FEET YET IT ALSO SHOWS 24 INCHES TO ONE SIDE OF THE |
| | WATER CLOSET AND 18 INCHES ON THE OTHER SIDE OF THE |
| | WATER CLOSET WHICH EQUALS 42 INCHES OVERALL. CLARIFY. |
| | 27) SHT. A-5.10 - SHOW THE CLEAR FLOOR SPACE DIMENSIONS |
| | ON THE FLOOR PLAN. COMPLY WITH ANSI A117.1 SECS. |
| | 4.16.2, 4.18 AND 4.19. SHOW THE CLEAR FLOOR SPACE FOR |
| | THE URINAL ON THE PLANS. |
| | 28) SHT. A-5.10 - THE RESTROOM ELEVATION DETAILS APPEAR |
| | TO SHOW THE GRAB BAR MEASUREMENT MEASURED TO THE BOTTOM |
| | OF THE GRAB BAR. GRAB BARS SHALL BE MEASURED TO THE |
| | CENTERLINE OF THE GRAB BAR PER ANSI A117.1 SEC. 4.16.4. |
| | 29) SHT. A-5.10 - THE URINAL SHALL BE LOCATED WITH THE |
| | RIM AT A MAXIMUM HEIGHT OF 17 INCHES ABOVE THE FLOOR |
| | PER ANSI A117.1 SEC.4.18.2. |
| | 30) SHT. A-5.10 - DELETE THE VERTICAL GRAB BAR FROM THE |
| | ELEVATION DETAILS. GRAB BARS SHALL BE INSTALLED IN THE |
| | HORIZONTAL POSITION. THERE IS NO EXCEPTION IN THE ANSI |
| | STANDARD FOR VERTICAL GRAB BARS. ANSI A117.1-1986 |
| | SEC.4.16.4. |
| | 31) SHT. A-5.10 - HANDICAP MOUNTING HEIGHT DETAILS (AT |
| | TOP OF DRAWING)- THE REAR GRAB BAR AT THE WATER CLOSET |
| | SHOWS A DIMENSION OF 3 FEET YET IT ALSO SHOWS 24 INCHES |
| | TO ONE SIDE OF THE WATER CLOSET AND 18 INCHES ON THE |
| | OTHER SIDE OF THE WATER CLOSET WHICH EQUALS 42 INCHES |
| | OVERALL. CLARIFY. |
| | B) THE GRAB BAR MEASUREMENT IS SHOWN TO THE TOP OF THE |
| | GRIPPING SURFACE. GRAB BARS SHALL BE MEASURED TO THE |
| | CENTERLINE OF THE BAR PER ANSI A117.1 SEC. 4.16.4 & |
| | FIGURE #29..REMOVE THE NOTE REFERRING TO THE TOP OF THE |
| | GRIPPING SURFACE. NOTE: THE MOUNTING DETAILS AT THE |
| | BOTTOM OF THE DRAWING APPEAR TO SSHOW THE GRAB BAR |
| | MEASUREMMENT TO THE BOTTOM OF THE GRAB BAR. DETAILS AT |
| | THE BOTOM OF THE DRAWING REFER TO ID DRAWINGS. THERE |
| | ARE NO SUCH DRAWINGS IN THIS SUBMITTAL. CLARIFY |
| | 32) SHT. A-5.10 - HANDICAP MOUNTING HEIGHTS - SHOW THE |
| | LOCATION OF THE GRAB BAR ADJACENT TO THE WATER CLOSET. |
| | COMPLY WITH ANSI A117.1 SEC.4.16.4 & FIGURE #29. |
| | 33) SHT. A-5.10 - THE SINK AND FAUCET IN THE LOUNGE |
| | SHALL COMPLY WITH ANSI A117.1 SEC. 4.19.2.2, 4.19.3, |
| | 4.19.5. SHOW THE CLEAR FLOOR SPACE ON THE PLAN WITH THE |
| | DIMESIONS. ALSO, INDICATE ON THE PLAN THAT THE LOUNGE |
| | IS LOCATED ON THE 8TH FLOOR.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 34) SHT. A-8.5 - DETAIL #15 - SUBMIT MANUFACTURER'S |
| | DETAILS/ INSTALLATION INSTRUCTIONS FOR THE FLUID |
| | APPLIED SHOWER PAN MATERIAL. THE MATERIAL SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.417.5.2.6. |
| | 35) SHT. A-8.5 - DETAIL #15 REFERS TO DETAIL #8 ON SHT. |
| | A-8.3. DETAIL #8 ON A-8.3 IS FOR A WINDOW SILL DETAIL. |
| | CLARIFY. |
| | 36) SHT. A-9.1 - DETAIL #1 - PLACE THE APPROVED LISTED |
| | ASSEMBLY SYSTEM NUMBER ON THE DETAIL. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 37) SHT. A-10.1 - UNIT A3 - WHICH DESIGN SPECIFICATION |
| | ( A OR B) OF THE FHA GUIDELINES APPLIES TO THIS UNIT? I |
| | CANNOT FIND ANY INFORMATION.CLARIFY. |
| | 38) SHT. A-10.2 - UNITS B1 & B1 MOD - THE CLEAR FLOOR |
| | SPACE FOR THE WATER CLOSET IN THE HALL BATH APPEARS TO |
| | BE IMPINGED UPON BY THE BATHROOM FRAMED DOOR OPENING. |
| | CLARIFY. |
| | 39) SHT. A-10.2 - UNIT B3 - HALL BATH - SHOW THE |
| | REQUIRED 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE |
| | THE SWING OF THE DOOR AS IT IS CLOSED AS REQUIRED BY |
| | THE FHA DESIGN MANUAL PAGE 7.39. |
| | 40) SHT. A-10.2 - UNIT B3 - THE DOOR TO THE LAUNDRY |
| | ROOM SHALL PROVIDE A 32 INCH CLEAR OPENING AS IT |
| | INTENDED FOR USER PASSAGE. FHA DESIGN MANUAL PAGE 7.19. |
| | 41) SHT A-10.2 - UNIT B3 - THE PLAN CALLS OUT TYPE A |
| | BATH FOR THE MASTER AND TYPE B BATH FOR THE HALL BATH. |
| | IF TYPE A, ALL BATHROOMS SHALL COMPLY FOR TYPE A SO YOU |
| | CANNOT HAVE A TYPE A AND TYPE B TOGETHER. CLARIFY. |
| | 42) SHT. A-10.3 - CLARIFY THE ACCESSIBILITY |
| | REQUIREMENTS FOR THE TOWNHOMES. MY UNDERSTANDING OF THE |
| | FAIR HOUSING ACT REQUIREMENTS DO NOT MANDATE COMPLIANCE |
| | FOR MULTISTORY TOWNHOMES. TO BE A COVERED UNIT, ALL OF |
| | THE FINISHED LIVING SPACE MUST BE ON THE SAME FLOOR |
| | EXCEPT WHEN THEY ARE LOCATED IN BUILDINGS WHICH HAVE |
| | ONE OR MORE ELEVATORS, IN WHICH CASE, THE PRIMARY ENTRY |
| | IS COVERED. FHA DESIGN MANUAL PAGE 7. |
| | 43) SHT. A-10.4 - THE FAIR HOUSING DETAILS AT THE LOWER |
| | RIGHT OF THE PLAN SHOW THE DEPTH OF THE LAVATORIES AS |
| | 25 INCHES. THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE |
| | 24 INCHES PER THE FHA DESIGN MANUAL PAGES 7.43 & 7.44. |
| | 44) SHT. A-10.4 - EQUIPMENT MOUNTING DETAILS - THERE IS |
| | A NOTE THAT REFERS TO THE 2014 F.A.C. SEC. 308. THE |
| | 2017 CODE IS THE CODE IN EFFECT. THESE ITEMS MAY FALL |
| | UNDER THE ANSI A117.1 STANDAED. |
| | 45) SHT. A-10.4 - TUB GRAB BAR REINFORCEMENT DETAILS - |
| | IDENTIFY THE FOOT AND HEAD OF THE TUB FOR THE DETAILS |
| | SHOWING THE 24 INCH WIDE REINFORCEMENT. COMPLY WITH FHA |
| | DESIGN MANUAL PAGES 6.8 & 6.9. |
| | 46) SHT. A-10.4 - SUBMIT A GRAB BAR REINFORCEMENT |
| | DETAIL FOR THE SHOWERS. FHA DESIGN MANUAL PAGE 7.56. |
| | 47) SHT. A-10.5 - THE COMMON AREAS SHALL COMPLY WITH |
| | ANSI A117.1 PER THE FHA DESIGN MANUAL REQUIREMENT #2, |
| | PAGE 2.5. PLACE A NOTE ON THE PLAN REFERENCING THE ANSI |
| | STANNDARD AND REMOVE REFERENCE TO THE FLORIDA BUILDING |
| | CODE - ACCESSIBILITY.. THE PLANS REFERENCE THE 2014 |
| | FBC-ACCESS. WHICH IS NOT APPLICABLE. |
| | 48) SHT. A-10.5 - THE ELEVATION DETAILS FOR THE WATER |
| | CLOSETS SHOW THE GRAB BARS MEASURED TO THE CENTERLINE |
| | OF THE GRAB BAR BUT THE TEXT STATES " TOP OF GRIPPING |
| | SURFACE." THE ANSI STANDARD SHOWS GRAB BARS MEASURED TO |
| | THE CENTERLINE. CLARIFY. |
| | 49) SHT. A-5.9 - WOMEN'S RESTROOM #A-0126 - TOILET ROOM |
| | ENLARGEMENT PLAN - THERE ARE TWO HANDICAP ACCESSIBLE |
| | TOILET ROOMS SHOWN BUT ONE OF THE TOILET ROOMS DOES NOT |
| | HAVE A LAVATORY WITHIN THE TOILET ROOM. CLARIFY. ALSO, |
| | THE DOOR CANNOT SWING INTO THE CLEA FLOOR SPACE FOR THE |
| | WATER CLOSET PER FBC-ACCESS. SEC.603.2.3.( SEE |
| | EXCEPTION #2 - SHOW THE CLEAR FLOOR SPACE AND THE |
| | DIMENSIONS). |
| | 50) SHT. A-5.9 - MEN'S TOILET ROOM #A-0125 - THE DOOR |
| | CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORY. FBC-ACCESS. SEC.603.2.3.( SEE EXCEPTION #2 - |
| | SHOW THE CLEAR FLOOR SPACE AND THE DIMENSIONS). |
| | 51) SUBMIT A DETAIL OF THE DOMESTIC BOOSTER PUMP |
| | SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 52) SUBMIT A SANITARY RISER DIAGRAM OF THE COMPLETE |
| | UNDERGROUND SANITARY COLLECTION SYSTEM WITH ALL |
| | VERTICAL RISER LINES IDENTIFIED WITH RISER TAGS. SHOW |
| | THE SLOPE OF THE SANITARY LINES. COMPLY WITH |
| | FBC-PLUMBING TABLE 710.1 (1). WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. |
| | 53) SHT. P-2.0A - KEYNOTE #6 REFERS TO A DETAIL BUT |
| | THERE IS NO SPECIFIC DETAIL REFERENCED. ( DRAWING #, |
| | DETAIL #). CLARIFY. |
| | 54) SHT. P-2.0A - IDENTIFY ALL RISERS WITH RISER TAGS, |
| | INCLUDING THE VENTS/DRY VENTS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 55) THE WATER SUPPLY VALVES FOR THE STACKED |
| | WASHER/DRYER UNITS SHALL BE PROVIDED WITH ACCESS PER |
| | FBC-PLUMBING SEC. 606.3. |
| | 56) SUBMIT A COMPLETE RAIN WATER RISER AND UNDERGROUND |
| | COLLECTION SYSTEM.ALL VERTICAL RISSER LINES SHALL BE |
| | IDENTIFIED WITH RISER TAGS. THE SIZING OF THE SYSTEM |
| | SHALL INCLUDE THE AREA OF ALL VERTICAL WALLS THAT |
| | DIVERT RAINWATER TO THE ROOF IN ACCORDANCE WITH |
| | FBC-PLUMBING SEC.1106.4, WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. |
| | 57) SHT. P-2.0A & P-2.B - THE MATCH LINES NOTED ON THE |
| | PLANS APPEAR TO BE INCORRECT. CLARIFY. |
| | 58) SHT.P-2.0B - IDENTIFY FIXTURE OI-1 CONNECTED TO THE |
| | FLOOR DRAINS.THIS FIXTURE IS NOT LISTED ON THE PLUMBING |
| | FIXTURE SCHEDULE AND SUBMIT A DETAIL FOR THIS ITEM.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 59) SHT. P-2.0B - IDENTIFY THE SANITARY AND VENT RISERS |
| | WITH RISER TAGS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 58) SHT. P-2.0B - THE MATCH LINES AT THE TOP OF THE |
| | PAGE APPEAR TO BE INCORRECT. SHT. P-2.0B SHOWS SANITARY |
| | LINES AND SHT. P-2.0C SHOWS WATER LINES. CLARIFY. |
| | 60) SHT. P-2.0C - PROVIDE A MATCHLINE ON THE RIGHT SIDE |
| | OF THE PLAN FOR THE CONTINUATION OF THE 6 INCH SANITARY |
| | LINE WITH 152 DFU'S EXITING UNIT B3. |
| | 61) SHT. P-2.1A - IDENTIFY ALL THE STORM RISERS WITH |
| | RISER TAGS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 62) DRAWING SERIES P-2.1 THROUGH P-2.8 - PLACE A RISER |
| | TAG ON THE 2 INCH VENT LINE AS REFERENCED IN KEYNOTE #1 |
| | AND TAG THE RAIN WATER RISERS ON THE APPLICABLE |
| | DRAWINGS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 63) SHT. P-2.1C - KEYNOTE #4 STATES "4 INCH STORM PIPE |
| | DOWN" BUT THE ARROW IS POINTING TO A WATER BRANCH LINE. |
| | CLARIFY. |
| | 64) SHT. P-2.1D - KEYNOTE #5 - LIST THE SPECIFIC |
| | DRAWING NUMBER IN THE FOOTNOTE FOR THE CONTINUATION OF |
| | THE WATER AND SANITARY LINES.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 65) SHTS. P-2.2C, P-2.3B & P-2.3C- SUBMIT THE |
| | APPLICABLE KEYNOTE LEGEND FOR THESE PLANS. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 66) SHT. P-2.8A - UNITS A2 - THERE ARE TWO RISERS SHOWN |
| | AT THE WASHING MACHINE BUT THERE IS NO RISER TAG ON ONE |
| | OF THE RISERS. CLARIFY. |
| | 67) SHT. P-2.8A - UNITS A2 - THERE IS A RISER TAG 4/S |
| | BEHIND THE WATER CLOSET BUT NO RISER IS SHOWN. CLARIFY. |
| | 68) SHT. P-5.1 - KEYNOTE #3 - STATE THE SPECIFIC |
| | DRAWING NUMBER FOR THE CONTINUATION OF THE WATER |
| | LINE.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 69) SHTS. P-4.1 7 P-4.2 - KEYNOTE 39 REFERS TO AIR |
| | ADMITTANCE VALVES BUT NOTHING IS SHOWN ON THE PLANS. |
| | CLARIFY. NOTE: WHERE THE HORIZONTAL BRANCH IS LOCATED |
| | MORE THAN 4 BRANCH INTERVALS FROM THE TOP OF THE STACK, |
| | THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF |
| | VENT THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, |
| | OR EXTEND OUTDOOR TO THE OPEN AIR PER FBC-PLUMBING |
| | SEC.918.3.1. |
| | 70) SHT.P-5.1 - THE FLOOR DRAIN IN THE PAVILION EXCEEDS |
| | THE DISTANCE TO A VENT PER FBC-PLUMBING SEC.909.1 7 |
| | TABLE 909.1. |
| | 71) SHT. P-5.1 SHOWS AN AIR ADMITTANCE VALVE ON THE |
| | SINK.THE USE OF AN AIR ADMITTANCE MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, IT SHALL OMPLY |
| | WITH FBC-PLUMBING SEC.918.3.1.WHERE THE HORIZONTAL |
| | BRANCH IS LOCATED MORE THAN 4 BRANCH INTERVALS FROM THE |
| | TOP OF THE STACK, THE HORIZONTAL BRANCH SHALL BE |
| | PROVIDED WITH A RELIEF VENT THAT SHALL CONNECT TO A |
| | VENT STACK OR STACK VENT, OR EXTEND OUTDOOR TO THE OPEN |
| | AIR PER FBC-PLUMBING SEC.918.3.1. |
| | 72) SHT. P-5.1 - PROVIDE A SANITARY AND WATER RISER |
| | DIAGRAM FOR THE TOILET ROOMS AND SINK AT THE POOL DECK. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 73) THERE IS A FIRE PIT SHOWN ON SHT. A-2.1A. IS THIS |
| | FFIRE PIT GAS? IF SO, SUBMIT A GAS RISER DIAGRAM FOR |
| | ANY AND ALL GAS PIPING THAT WILL BE INSTALLED IN THIS |
| | BUILDING.WPB AMEND. TO FBC SEC. 107.3.5.1.5. ALSO, |
| | SUBMIT COMBUSTION AIR CALCCULATIONS FOR ANY |
| | EQUIPMENT/APPLIANCES LOCATED ON THE INTERIOR OF THE |
| | STRUCTURE. |
| | 74) SHT.P-5.2 - THE WATER CLOSETS IN THE WOMEN'S |
| | RESTROOM ARE NOT PROPERLY VENTED. THE VENT SHALL BE |
| | LOCATED BETWEEN THE TWO WATER CLOSETS.FBC-PLUMBING SEC. |
| | 901.2, |
| | 75) SHT. P-6.1 - RISER #4/S - TRAPS ARE MISSING ON THE |
| | SHOWERS. |
| | 76) SHT. P-6.1 - RISER #5/S - THE RISER DECREASES IN |
| | PIPE SIZE FROM 3 INCHES TO 2 1/2 INCHES IN THE |
| | DIRECTION OF FLOW AT THE BOTTOM OF THE STACK. |
| | FBC-PLUMBING SEC. 704.2. CLARIFY. |
| | 77) SHT. P-6.1 - RISER #8/S - SIZE THE RISER. |
| | 78) SHT. P-6.2 - RISER#10/S - SHOWS A 3 INCH STACK AND |
| | A 2 INCH VTR. THE VENT THROUGH THE ROOF SHALL BE 3 |
| | INCHES PER FBC-PLUMBING SEC.913.3. |
| | 79) SHT. P-8.1 - WATER HEATER DETAIL - INICATE ON THE |
| | DETAIL THE TYPE OF PIPE MATERIAL TO BE USED FOR THE PAN |
| | DRAIN AND THE THERMAL INSULATION ON THE HOT WATER |
| | LINE.THE PAN DRAIN MATERIAL SHALL COMPLY WITH THE |
| | FBC-MECH. SECS.602.2.1 & 602.2.1.7. |
| | 80) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | SUBMETERS BEING INSTALLED. IF THEY ARE BEING INSTALLED |
| | IN THE MECHANICAL CLOSET, THEY SHALL COMPLY WITH |
| | FBC-MECH. SECS. 602.2.1 & 602.2.1.7. |
| | 81) INDICATE ON THE PLANS (SHT. A-8.5) IF THE TRASH |
| | CHUTE WILL BE EQUIPPED WITH A FLUSHING RING AT THE TOP |
| | OF THE CHUTE. IF SO, SUBMIT A DETAIL FOR THE WATER |
| | CONNECTION. IF A CHEMICAL SOLUTION WILL BE CONNECTED TO |
| | THE SYSTEM, A BACKFLOW DEVICE SHALL BE REQUIRED. |
| | FBC-PLUMBING SEC.608.1. |
| | |