| Date |
Text |
| 2021-02-19 13:58:00 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT- 20120712 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE |
| | FBC FG- FLORIDA FUEL GAS CODE |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) THIS IS A MULTIFAMILY APARTMENT BUILDING PLEASE |
| | EXPLAIN THE USE OF ?GUEST ROOMS (HOTEL) IN THE ENERGY |
| | CALCULATIONS. FBC M TABLE 403.3.1.1 |
| | |
| | 2) PLEASE PROVIDE VENTILATION CALCULATIONS FOR EACH |
| | DWELLING UNIT. FBC M 401.2 |
| | |
| | 3) THE DUCTWORK COMING OUT OF THE RATED SHAFT IN THE |
| | CORRIDORS SHOULD BE PROTECTED BY A FSD BUT THE SYMBOL |
| | THAT IS IN THE LOCATION DOES NOT APPEAR ON SHEET M-0.1. |
| | PLEASE IDENTIFY THE CORRECT DAMPER FOR THE DUCTWORK |
| | PENETRATING THE RATED SHAFT. FBC M 607 |
| | |
| | 4) PLEASE IDENTIFY THE RTU FOR THE DUCTWORK PENETRATING |
| | THE SHAFTS IN THE CORRIDORS AT EACH FLOOR. FBC 107.2.1 |
| | |
| | 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH |
| | SPACE IN THESE BUILDINGS. FBC M 403.3.1.1 |
| | |
| | 6) PLEASE PROVIDE A COMPLETE OUTDOOR AIR CALCULATION |
| | FOR THE RETAIL TENANT SPACE. FBC TABLE 403.3.1.1 |
| | |
| | 7) PLEASE PROVIDE THE CFM?S SUPPLIED BY THE REGISTER IN |
| | THE CORRIDOR CLOSE TO THE A1 UNITS ON THE LEFT SIDE OF |
| | THE PAGE. FBC 107.2.1 |
| | |
| | 8) TYPICAL UNIT SHEETS: PLEASE PROVIDE THE MAKE AND |
| | MODEL OF THE SPECIFIC DRYER USED IN EACH UNIT. FBC M |
| | 504.8.4.2 |
| | |
| | 9) TYPICAL UNITS SHEETS: PLEASE PROVIDE THE DRYER DUCT |
| | LENGTHS INCLUDING THE 45 AND 90 DEGREE ELBOWS. FBC M |
| | 504.8.5 |
| | |
| | 10) TYPICAL UNITS SHEETS: PLEASE VERIFY THE EXHAUST IS |
| | A MINIMUM OF 3? FROM ANY OPERABLE OPENING INTO THE |
| | UNITS. FBC M 501.3.1 (3) |
| | |
| | 11) TYPICAL UNITS SHEETS: DOES NOTE (8) REFER TO THE |
| | MECHANICAL CLOSET DOORS? IF SO EITHER LABEL EACH DOOR |
| | OR ADD THE WORDS TO NOTE 8 THAT THIS IS THE MECHANICAL |
| | CLOSET DOOR AS SOME DOORS DO NOT HAVE THE FOOTNOTE 8 |
| | LABELED ON THE UNIT DRAWINGS. FBC 107.2.1 |
| | |
| | 12) SHEET M-4.2: UNIT B1 IS SUPPLYING 860 CFM OF AIR TO |
| | THE UNIT BUT SHEET M-7.1 INDICATES THAT AHU-B ONLY |
| | SUPPLIES 800 CFM OF SUPPLY AIR. PLEASE CORRECT THIS. |
| | FBC 107.2.1 |
| | |
| | 13) SHEET M-4.2: UNIT B3; PLEASE SHOW CFM OF SUPPLY AIR |
| | TO CLOSET, THE CFM?S HAVE NOT BEEN INCLUDED IN THIS |
| | VERSION. FBC 107.2.1 |
| | |
| | 14) SHEET M-4.2: UNIT B3; THE SUPPLY AIR IS 830 CFM, |
| | AHU-B ONLY SUPPLIES 800 CFM. PLEASE CORRECT THIS. FBC |
| | 107.2.1 |
| | |
| | 15) SHEET M-4.3: THE UNIT-C TH INDICATES AHU-C IS |
| | SUPPLYING 1210 CFM OF AIR. SHEET M-7.1 INDICATES AHU-C |
| | ONLY SUPPLIES 1050 CFM. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 16) SHEET M-5.2: AHU-3 IS SUPPLYING 2135 CFM OF AIR BUT |
| | SHEET M-7.1 INDICATES AHU-3 ONLY SUPPLIES 1900 CFM. |
| | PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 17) SHEET M-7.1: RTU-3 INDICATES A MAX. OF SUPPLY AIR |
| | IS 2,450 CFM. THE TOTAL OF SUPPLY AIR FOR EACH FLOOR IS |
| | 2,800CFM. PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |