| Plan Review Notes For Permit 20120703 |
| Permit Number |
20120703 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-30 15:24:24 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | | PERMIT- 20120703 | | | 12/30/2020 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER- FBC-17 RES. FUEL GAS. | | | A) PROVIDE THE TYPE AND SIZE OF MAIN SUPPLY PIPE FROM | | | THE METER TO THE APPLIANCES- SECTION G2413.3. | | | B) SHOW THE BTUH LOAD OF THE POOL HEATER AND ADD THE | | | LOAD TO THE TOTAL LOAD OF THE SYSTEM- SECTION G2413.2. | | | C) PROVIDE THE TOTAL LENGTH OF THE SYSTEM FROM THE | | | METER TO THE MOST REMOTE OUTLET- SECTIONS G2413.4.1 & | | | G2413.4.2. | | | D) PLEASE LIST THE PIPE SIZING TABLES ON THE DRAWING- | | | SECTION G2413.4. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|