| 2020-12-18 09:42:19 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. NEW EMERGENCY PANEL AND SUB PANEL SHOWN IN PANEL |
| | SCHEDULE. PROVIDE A NEW ELECTRICAL RISER DIAGRAHM. |
| | INCLUDE GROUNDING ELECTRODE SYSTEM. |
| | PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC |
| | 107.2.1 |
| | |
| | 2. PANEL SCHEDULE SUBMITTED FOR REVIEW DOES NOT INCLUDE |
| | NEW RANGE AND HOOD CIRCUTS AND GAS W/H IGNITER CIRCUT. |
| | ALSO PROVIDE THE CONDUCTOR TYPE, WIRE SIZE AND V.A. OF |
| | EACH CIRCUT. |
| | PANEL SCHEDULE: |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902. |
| | |
| | 3. LOAD CALC'S SUBMITTED FOR REVIEW DO NOT INCLUDE THE |
| | POOL EQUIPMENT, NEW SUB PANEL AND NEW EMERGENCY PANEL. |
| | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | |
| | 4. R404.1LIGHTING EQUIPMENT (MANDATORY). |
| | NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY |
| | HIGH-EFFICACY LAMPS. |
| | EXCEPTION: LOW-VOLTAGE LIGHTING. |
| | A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| | |
| | 5. PROVIDE OUTLET AT FRONT OF STRUCTURE. |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | |
| | 6. AN OUTLET IS REQUIRED ON THE SIDE OF THE NEW CLOSET |
| | IN THE FAMILY ROOM. |
| | E3901.2.2 WALL SPACE. |
| | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE |
| | FOLLOWING: [210.52(A)(2)] |
| | 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH, |
| | INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS |
| | UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR |
| | OPENINGS, FIREPLACES, AND FIXED CABINETS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |