Plan Review Notes
Plan Review Notes For Permit 20120644
Permit Number 20120644
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-16 12:28:4412/16/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM AND DO THE
 NEW PLUMBING DO THE INFORMATION PROVIDE THIS MAY CHANGE
 WHEN FLOORS ARE OPEN, THIS CAN BE REVISED BEFORE FINAL
 PLUMBING PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (11) RESIDENTIAL PLUMBING.
  
 2. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 5. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved