Plan Review Notes
Plan Review Notes For Permit 20120644
Permit Number 20120644
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-21 15:45:58SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 DESIGNER FBC WPB 107.1
 2) PLEASE SHOW THE CEILING HEIGHT AT THE NEW CEILING
 FRAMING TO COMPLY WITH FBC R305.1
 3) PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS
 THROUGHOUT THE HOUSE TO COMPLY WITH FBC R314.2.2
 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  