| Plan Review Notes For Permit 20120638 |
| Permit Number |
20120638 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-18 08:11:36 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL THAT | | | SHOWS THE DESIGN WIND PRESSURES NEEDED SHOWN ON DRAWING | | | (S1) - FBC R905.15.3 APPLICATION. | | | LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE | | | WITH THIS CHAPTER AND THE MANUFACTURER?S INSTRUCTIONS. | | | THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE | | | LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER | | | THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE | | | R301.2(2). |
|