Plan Review Notes
Plan Review Notes For Permit 20120625
Permit Number 20120625
Review Stop B
Sequence Number 2
Notes
Date Text
2021-03-16 10:20:32SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ALL DRAWING IN PROJECTDOX THAT ARE NOT SIGNED AND
 SEALED BY THE ARCHITECT NEED TO BE SIGNED AND SEALED BY
 THE ARCHITECT.
 2) LOCATIONS OF THE SMKE ALARMS THROUGH OUT THE
 EXISTING HOUSE ARE NOT SHOWN ON DRAWING E1 AS THE
 COMMENT LETTER STATES - PLEASE SHOW THE LOCATIONS OF
 THE REQUIRED SMOKE ALARMS THROUGHOUT THE EXISTING HOUSE
 TO COMPLY WITH FBC R314.2.2 ALTERATIONS, REPAIRS AND
 ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  