| Plan Review Notes For Permit 20120625 |
| Permit Number |
20120625 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-20 15:21:43 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) THE CODE IN EFFECT HAS CHANGED ON JAN. 1 2021 - | | | PLEASE REVISE THE DRAWINGS TO SHOW THE DESIGN BASED ON | | | 2020 FBC AND ASCE 7-16. | | | 2) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT. | | | 3) PLEASE SHOW THE LOCATIONS OF THE REQUIRED SMOKE | | | ALARMS THROUGHOUT THE EXISTING HOUSE TO COMPLY WITH FBC | | | R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | |
|